Plan Review Notes
Plan Review Notes For Permit 20080382
Permit Number 20080382
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-04 13:22:2309/04/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THERE IS NO EXISTING PERMIT FOR THIS STRUCTURE ON FILE
 AND WORK MAY HAVE BEEN DONE WITHOUT A PERMITS OR
 INSPECTIONS. THE STRUCTURE WAS AN EXISTING GARAGE AT
 ONE POINT. THE WORD EXISTING OF ITEMS DOES NOT
 CONSTITUTE PERMITTED WORK SO A FULL EVALUATION AND
 REQUIRED INSPECTION WILL TAKE PLACE ALONG WITH PLANS
 AND SPORTING DOCUMENTS.
  
 1. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  
 2. A REDUCED PRESSURE ZONE ASSEMBLY REQUIRED SINCE THIS
 A DUAL DWELLING PER THE CITY OF WEST PALM BEACH ORD
 #2853-95. A PERMIT REQUIRED BY A LICENSED CONTRACTOR
 AND MUST BE CERTIFIED BY UTILITIES PRIOR TO FINAL
 INSPECTION. PLEASE CONTACT THE CITY OF WPB UTILITIES AT
 561-822-2240 FOR FURTHER DIRECTIONS.
  
 3. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. PLEASE SHOW THE SOURCE OF HOT WATER FOR THE
 STRUCTURE PER THE 2017 FBC SEC. R 2722.2.
  
 5. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS PER THE 2017 FBC SEC.
 R2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 6. PLEASE SHOW WATER SERVICE SUPPLY AND SHUT OFF VALVE
 PER THE 2017 FBC SEC. R 306.4.
  
 7. PLEASE SHOW A CLEAN-OUT ON ISOMETRIC DIAGRAM FOR THE
 SEWER JUNCTION PER THE 2017 FBC SEC. 3005.2.3.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved