Plan Review Notes
Plan Review Notes For Permit 20080364
Permit Number 20080364
Review Stop P
Sequence Number 3
Notes
Date Text
2020-11-09 11:46:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20080364 991 BANYAN BLVD
  
 NOTE: A SEPARATE PERMIT AND REVIEW IS REQUIRED FOR THE
 IRRIGATION.
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
  
 1) OK
 2) OK
 3) PARTIALLY COMPLIED THE CORRECT DRAWING IS P-4.01.
 THE MEP RESPONSE NARRATIVE REFERS TO SHT. P-4.00. THERE
 IS NO SUCH DRAWING IN THE PLANS. IT APPEARS TO HAVE
 BEEN CHANGED TO P4.01. CLARIIFY.
  
 NEW COMMENT P-3.07 WATER DISTRIBUTION SHOWS DOMESTIC
 BOOSTER PUMP AND REFERS TO P-4.01 FOR PUMP SPECS.
 P-4.01 SHOWS DETAIL WITH A FRONT AND SIDE VIEW OF
 BOOSTER PUMP BUT NO SCHEDULE/MANUFACTURER'S
 SPECIFICATIONS. PER WPB FBC 107.2.1, PROVIDE A
 SCHEDULE/SPECIFICATION. SPECIFY MANUFACTURER, MODEL,
 GPM, OPERATING PRESSURE, TDH, PUMP MOTOR ELECTRICAL
 CHARACTERISTICS, MOTOR CONTROLLER AND ANY OTHER ITEMS
 REQUIRED TO PROVIDE A FULLY OPERATIONAL PUMP SYSTEM.
 ALSO SEE COMMENT 39 BELOW.
  
 4) OK
 5) OK. THE RESPONSE NARRATIVE FOR PLAN REVIEW COMMENT
 #13 REFERS TO ELEVATIONS #13 & #14 ON SHT. A-5.05.
 THERE ARE NO SUCH ELEVATIONS ON THIS SHEET. CLARIFY.
  
 NEW COMMENT: A-5.05/ACCESSIBLE BATHROOM FIXTURE
 LEGEND-P3; CENTER LINE OF WATER CLOSET SHALL BE MIN 16
 INCHES/MAX 18 INCHES FROM SIDE WALL, SPACE FROM
 SIDEWALL TO BEGINNING OF HAND RAIL SHALL BE 6 INCHES
 MAXIMUM.
  
 6) OK
 7) OK
 8) OK
 9) OK
 10) OK
 11) OK
 12) OK
 13) OK. SHT. A-8.00A - COMMON AREAS FINISH SCHEDULE -
 SHOWS THE WALLS IN THE 3RD FLOOR RESTROOMS TO BE GYPSUM
 BOARD WITH WALLPAPER FINISH. WALLS AND PARTITIONS
 WITHIN TWO FEET OF WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR AND THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. EPOXY PAINT DOES NOT MEET THIS
 REQUIREMENT.FBC-BUILDING SEC. 1210.2.2.
 FOR CLARIFICATION DETAIL P12/A-5.05 SHOWS HEIGHT OF
 TILE WALL, NOT DETAIL P4.
  
 NEW COMMENT: WALL FINISH IN JANITOR'S CLOSET IS EXPOSED
 CONCRETE/ CMU BLOCK. PER FBC 1210.2.2, PROVIDE A
 NONABSORBANT FINISH AS CONCRETE IS POUROUS.
  
 14) OK
 15) OK
 16) SECOND REQUEST: SHT. P-1.00 - SHOW THE CONTINUATION
 POINT/ ORIGINATION POINT OF THE FUTURE 1 1/4 INCH
 CONDENSATE DRAIN STUB OUT AT THE FUTURE RETAIL SPACE.
 THERE IS ANOTHER LINE NEXT TO THIS CONDENSATE LINE THAT
 IS NOT IDENTIFIED OR SHOWS A PIPE SIZE. REFER TO COLUMN
 LINES A-B/3-4.
 TO BE CLEAR, WHAT IS THE CAPPED LINE ADJACENT TO THE
 CONDENSATE DRAIN AT GRID LINE 3 BETWEEN A / B AND WHERE
 DOES IT CONTINUE TO?
 17) OK
 18) SECOND REQUEST: SHT. P-1.00 - SHOW THE CONTINUATION
 POINT OF THE 10 INCH STORM DRAIN AND THE 1 1/4 INCH
 CONDENSATE LINE AT GRID LINE D-E/15.
 TO BE CLEAR, DO THE CIVIL DRAWINGS ADDRESS THIS AND
 DOES THE CONDENSATE TERMINATE TO DRYWELL OR CONNECT TO
 THE STORM. PROVIDE GUIDANCE AND DETAIL; INCLUDE
 REFERENCE TO CIVIL DRAWINGS.
 19) SECOND REQUEST: SHT.P-1.00- SIZE THE STORM,
 SANITARY, WATER LINES ON THE PLANS. PIPE SIZES ARE
 MISSING IN QUITE A FEW AREAS. WPB AMEND. TO FBC SEC.
 107.2.1.
 PLEASE NOTE, SIZES OF WATER DISTRIBUTION BRANCHES TO
 RETAIL, RESTROOMS, BREAK ROOM AND JANITOR'S CLOSET ARE
 AMONG SIZES MISSING. IT IS NOTED THAT THESE BRANCHES
 ARE SIZED ON NEW P-3.07, DOMESTIC WATER PIPING
 DISTRIBUTION DIAGRAM. PER WPB FBC 107.2.1, PROVIDE THE
 SIZING OF THE WATER BRANCHES AND ANY OTHER PIPING THAT
 IS NOT SIZED.
 20) OK
 21) OK
 22) OK
 23) OK
 24) OK
 25) OK
 26) OK
 27) OK
 28) OK
 29) OK
 30) OK
 31) OK
 32) SECOND REQUEST: SHT.P-3.04 ? PLACE THE SLOPE OF THE
 HORIZONTAL STORM DRAIN PIPING ON THE PLAN. COMPLY WITH
 FBC-PLUMBING ABLE 1106.2. TO BE CLEAR, SLOPE SHALL BE
 IN ACCORDANCE WITH FBC PL TABLE 1106.2 FOR HORIZONTAL
 STORM DRAINS, NOT AS REQUIRED IN FBC PL CHAPTER 7 FOR
 HORIZONTAL SANITARY DRAINS.
 33) SHT. P-3.06 - SIZE ALL SECTIONS OF THE SANITARY
 COLLECTION SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. OK
  
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN
 SHEET P-1.00 AND P-3.06 AT CLEAN OUT AT GRID LINES
 A/4-5 TO REFER TO CIVIL DRAWINGS SIMILAR TO NOTE
 PROVIDED AT GRIDLINES A/10.
  
 34) SECOND REQUEST: SHT. P-4.01-FIXTURE CONNECTION
 SCHEDULE NOTE #1 REFERS TO MIAMI-DADE CODE SECTION
 8-31. DELETE THIS REFERENCE FROM THE NOTE.
 35) OK
 36) OK
 37) OK
 38) THE SUBMETERS SHALL BE NON COMBUSTIBLE IF LOCATED
 IN A RETURN AIR CLOSET AS IT APPEARS THEY ARE. THE
 SUBMITTED SPECS FOR THE METER DOES NOT SHOW THIS. THESE
 METERS ARE COMPOSED OF A POLYMER MATERIAL. RAPPING THE
 SUBMETERS WITH A FIRE WRAP IS NOT AN OPTION. NOTE HAS
 BEEN ADDED BY ENGINEER TO REQUIRE UNIT TO BE NON
 COMBUSTIBLE; HOWEVER PER WPB FBC 107.2.1, A SCHEDULE
 AND MANUFACTURER'S SPECIFICATION FOR A NON COMBUSTIBLE
 UNIT SHALL BE PROVIDED.
 39) SECOND REQUEST: ALSO SEE NEW COMMENT ADDED AT
 COMMENT 3 ABOVE. SUBMIT ADDITIONAL INFORMATION/DETAILS
 ON THE BOOSTER PUMP. THE DETAIL ON SHT. P-4.01 IS VERY
 MINIMAL. WPB AMEND. TO FBC SEC. 107.2.1.
 TO BE CLEAR, P-3.07 WATER DISTRIBUTION SHOWS DOMESTIC
 BOOSTER PUMP AND REFERS TO P-4.01 FOR PUMP SPECS.
 P-4.01 SHOWS DETAIL WITH A FRONT AND SIDE VIEW OF
 BOOSTER PUMP BUT NO SCHEDULE/MANUFACTURER'S
 SPECIFICATIONS. PER WPB FBC 107.2.1, PROVIDE A
 SCHEDULE/SPECIFICATION. SPECIFY MANUFACTURER, MODEL,
 GPM, OPERATING PRESSURE, TDH, PUMP MOTOR ELECTRICAL
 CHARACTERISTICS, MOTOR CONTROLLER AND ANY OTHER ITEMS
 REQUIRED TO PROVIDE A FULLY OPERATIONAL PUMP SYSTEM.
 40) OK
  
 NEW COMMENT:
 PER WPB FBC 107.2.1, PROVIDE ON P-1.00, P-1.02 AND
 P-3.07, WATER CONNECTIONS TO IRRIGATION. COORDINATE
 WITH IP-101 AND IP-102. INDICATE ON THE PLANS THE
 REQUIRED BACKFLOW PREVENTION DEVICES OR PROVIDE
 NOTATION WHERE BACKFLOW PREVENTION DEVICES ARE PROVIDED
 BY THE LANDSCAPE/IRRIGATION DRAWINGS. ADDITIONALLY,
 CIVIL DRAWING C-9 SHALL COORDINATE AS THERE APPEARS TO
 BE A METER ON IP-101.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  