| 2020-11-09 11:46:35 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20080364 991 BANYAN BLVD |
| | |
| | NOTE: A SEPARATE PERMIT AND REVIEW IS REQUIRED FOR THE |
| | IRRIGATION. |
| | |
| | 3RD REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1) OK |
| | 2) OK |
| | 3) PARTIALLY COMPLIED THE CORRECT DRAWING IS P-4.01. |
| | THE MEP RESPONSE NARRATIVE REFERS TO SHT. P-4.00. THERE |
| | IS NO SUCH DRAWING IN THE PLANS. IT APPEARS TO HAVE |
| | BEEN CHANGED TO P4.01. CLARIIFY. |
| | |
| | NEW COMMENT P-3.07 WATER DISTRIBUTION SHOWS DOMESTIC |
| | BOOSTER PUMP AND REFERS TO P-4.01 FOR PUMP SPECS. |
| | P-4.01 SHOWS DETAIL WITH A FRONT AND SIDE VIEW OF |
| | BOOSTER PUMP BUT NO SCHEDULE/MANUFACTURER'S |
| | SPECIFICATIONS. PER WPB FBC 107.2.1, PROVIDE A |
| | SCHEDULE/SPECIFICATION. SPECIFY MANUFACTURER, MODEL, |
| | GPM, OPERATING PRESSURE, TDH, PUMP MOTOR ELECTRICAL |
| | CHARACTERISTICS, MOTOR CONTROLLER AND ANY OTHER ITEMS |
| | REQUIRED TO PROVIDE A FULLY OPERATIONAL PUMP SYSTEM. |
| | ALSO SEE COMMENT 39 BELOW. |
| | |
| | 4) OK |
| | 5) OK. THE RESPONSE NARRATIVE FOR PLAN REVIEW COMMENT |
| | #13 REFERS TO ELEVATIONS #13 & #14 ON SHT. A-5.05. |
| | THERE ARE NO SUCH ELEVATIONS ON THIS SHEET. CLARIFY. |
| | |
| | NEW COMMENT: A-5.05/ACCESSIBLE BATHROOM FIXTURE |
| | LEGEND-P3; CENTER LINE OF WATER CLOSET SHALL BE MIN 16 |
| | INCHES/MAX 18 INCHES FROM SIDE WALL, SPACE FROM |
| | SIDEWALL TO BEGINNING OF HAND RAIL SHALL BE 6 INCHES |
| | MAXIMUM. |
| | |
| | 6) OK |
| | 7) OK |
| | 8) OK |
| | 9) OK |
| | 10) OK |
| | 11) OK |
| | 12) OK |
| | 13) OK. SHT. A-8.00A - COMMON AREAS FINISH SCHEDULE - |
| | SHOWS THE WALLS IN THE 3RD FLOOR RESTROOMS TO BE GYPSUM |
| | BOARD WITH WALLPAPER FINISH. WALLS AND PARTITIONS |
| | WITHIN TWO FEET OF WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET ABOVE THE FLOOR AND THE MATERIALS USED IN |
| | SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY |
| | AFFECTED BY MOISTURE. EPOXY PAINT DOES NOT MEET THIS |
| | REQUIREMENT.FBC-BUILDING SEC. 1210.2.2. |
| | FOR CLARIFICATION DETAIL P12/A-5.05 SHOWS HEIGHT OF |
| | TILE WALL, NOT DETAIL P4. |
| | |
| | NEW COMMENT: WALL FINISH IN JANITOR'S CLOSET IS EXPOSED |
| | CONCRETE/ CMU BLOCK. PER FBC 1210.2.2, PROVIDE A |
| | NONABSORBANT FINISH AS CONCRETE IS POUROUS. |
| | |
| | 14) OK |
| | 15) OK |
| | 16) SECOND REQUEST: SHT. P-1.00 - SHOW THE CONTINUATION |
| | POINT/ ORIGINATION POINT OF THE FUTURE 1 1/4 INCH |
| | CONDENSATE DRAIN STUB OUT AT THE FUTURE RETAIL SPACE. |
| | THERE IS ANOTHER LINE NEXT TO THIS CONDENSATE LINE THAT |
| | IS NOT IDENTIFIED OR SHOWS A PIPE SIZE. REFER TO COLUMN |
| | LINES A-B/3-4. |
| | TO BE CLEAR, WHAT IS THE CAPPED LINE ADJACENT TO THE |
| | CONDENSATE DRAIN AT GRID LINE 3 BETWEEN A / B AND WHERE |
| | DOES IT CONTINUE TO? |
| | 17) OK |
| | 18) SECOND REQUEST: SHT. P-1.00 - SHOW THE CONTINUATION |
| | POINT OF THE 10 INCH STORM DRAIN AND THE 1 1/4 INCH |
| | CONDENSATE LINE AT GRID LINE D-E/15. |
| | TO BE CLEAR, DO THE CIVIL DRAWINGS ADDRESS THIS AND |
| | DOES THE CONDENSATE TERMINATE TO DRYWELL OR CONNECT TO |
| | THE STORM. PROVIDE GUIDANCE AND DETAIL; INCLUDE |
| | REFERENCE TO CIVIL DRAWINGS. |
| | 19) SECOND REQUEST: SHT.P-1.00- SIZE THE STORM, |
| | SANITARY, WATER LINES ON THE PLANS. PIPE SIZES ARE |
| | MISSING IN QUITE A FEW AREAS. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | PLEASE NOTE, SIZES OF WATER DISTRIBUTION BRANCHES TO |
| | RETAIL, RESTROOMS, BREAK ROOM AND JANITOR'S CLOSET ARE |
| | AMONG SIZES MISSING. IT IS NOTED THAT THESE BRANCHES |
| | ARE SIZED ON NEW P-3.07, DOMESTIC WATER PIPING |
| | DISTRIBUTION DIAGRAM. PER WPB FBC 107.2.1, PROVIDE THE |
| | SIZING OF THE WATER BRANCHES AND ANY OTHER PIPING THAT |
| | IS NOT SIZED. |
| | 20) OK |
| | 21) OK |
| | 22) OK |
| | 23) OK |
| | 24) OK |
| | 25) OK |
| | 26) OK |
| | 27) OK |
| | 28) OK |
| | 29) OK |
| | 30) OK |
| | 31) OK |
| | 32) SECOND REQUEST: SHT.P-3.04 ? PLACE THE SLOPE OF THE |
| | HORIZONTAL STORM DRAIN PIPING ON THE PLAN. COMPLY WITH |
| | FBC-PLUMBING ABLE 1106.2. TO BE CLEAR, SLOPE SHALL BE |
| | IN ACCORDANCE WITH FBC PL TABLE 1106.2 FOR HORIZONTAL |
| | STORM DRAINS, NOT AS REQUIRED IN FBC PL CHAPTER 7 FOR |
| | HORIZONTAL SANITARY DRAINS. |
| | 33) SHT. P-3.06 - SIZE ALL SECTIONS OF THE SANITARY |
| | COLLECTION SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. OK |
| | |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN |
| | SHEET P-1.00 AND P-3.06 AT CLEAN OUT AT GRID LINES |
| | A/4-5 TO REFER TO CIVIL DRAWINGS SIMILAR TO NOTE |
| | PROVIDED AT GRIDLINES A/10. |
| | |
| | 34) SECOND REQUEST: SHT. P-4.01-FIXTURE CONNECTION |
| | SCHEDULE NOTE #1 REFERS TO MIAMI-DADE CODE SECTION |
| | 8-31. DELETE THIS REFERENCE FROM THE NOTE. |
| | 35) OK |
| | 36) OK |
| | 37) OK |
| | 38) THE SUBMETERS SHALL BE NON COMBUSTIBLE IF LOCATED |
| | IN A RETURN AIR CLOSET AS IT APPEARS THEY ARE. THE |
| | SUBMITTED SPECS FOR THE METER DOES NOT SHOW THIS. THESE |
| | METERS ARE COMPOSED OF A POLYMER MATERIAL. RAPPING THE |
| | SUBMETERS WITH A FIRE WRAP IS NOT AN OPTION. NOTE HAS |
| | BEEN ADDED BY ENGINEER TO REQUIRE UNIT TO BE NON |
| | COMBUSTIBLE; HOWEVER PER WPB FBC 107.2.1, A SCHEDULE |
| | AND MANUFACTURER'S SPECIFICATION FOR A NON COMBUSTIBLE |
| | UNIT SHALL BE PROVIDED. |
| | 39) SECOND REQUEST: ALSO SEE NEW COMMENT ADDED AT |
| | COMMENT 3 ABOVE. SUBMIT ADDITIONAL INFORMATION/DETAILS |
| | ON THE BOOSTER PUMP. THE DETAIL ON SHT. P-4.01 IS VERY |
| | MINIMAL. WPB AMEND. TO FBC SEC. 107.2.1. |
| | TO BE CLEAR, P-3.07 WATER DISTRIBUTION SHOWS DOMESTIC |
| | BOOSTER PUMP AND REFERS TO P-4.01 FOR PUMP SPECS. |
| | P-4.01 SHOWS DETAIL WITH A FRONT AND SIDE VIEW OF |
| | BOOSTER PUMP BUT NO SCHEDULE/MANUFACTURER'S |
| | SPECIFICATIONS. PER WPB FBC 107.2.1, PROVIDE A |
| | SCHEDULE/SPECIFICATION. SPECIFY MANUFACTURER, MODEL, |
| | GPM, OPERATING PRESSURE, TDH, PUMP MOTOR ELECTRICAL |
| | CHARACTERISTICS, MOTOR CONTROLLER AND ANY OTHER ITEMS |
| | REQUIRED TO PROVIDE A FULLY OPERATIONAL PUMP SYSTEM. |
| | 40) OK |
| | |
| | NEW COMMENT: |
| | PER WPB FBC 107.2.1, PROVIDE ON P-1.00, P-1.02 AND |
| | P-3.07, WATER CONNECTIONS TO IRRIGATION. COORDINATE |
| | WITH IP-101 AND IP-102. INDICATE ON THE PLANS THE |
| | REQUIRED BACKFLOW PREVENTION DEVICES OR PROVIDE |
| | NOTATION WHERE BACKFLOW PREVENTION DEVICES ARE PROVIDED |
| | BY THE LANDSCAPE/IRRIGATION DRAWINGS. ADDITIONALLY, |
| | CIVIL DRAWING C-9 SHALL COORDINATE AS THERE APPEARS TO |
| | BE A METER ON IP-101. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20080364 991 BANYAN BLVD |