Plan Review Notes
Plan Review Notes For Permit 20080364
Permit Number 20080364
Review Stop P
Sequence Number 2
Notes
Date Text
2020-10-23 11:00:241) THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO
 WHICH DESIGN SPECIFICATION ( A OR B) OF THE FAIR
 HOUSING ACT THE UNIT BATHROOMS WERE DESIGNED. IF
 SPECIFICATION A IS SELECTED AS THE BASIS FOR DESIGNING
 A BATHROOM, ALL BATHROOMS IN THE DWELLING UNIT ALSO
 MUST COMPLY WITH THE A SPECIFICATION. IF SPECIFICATION
 B IS SELECTED, ONLY ONE BATHROOM IN THE DWELLING UNIT
 MUST MEET THOSE REQUIREMENTS. I COULD NOT FIND THIS
 INFORMATION ANYWHERE ON THE ARCHITECTURAL OR PLUMBING
 SHEETS. 2ND REQUEST.
 2) INDICATE ON THE PLANS WHICH DESIGN STANDARD IS BEING
 USED FOR FAIR HOUSING ACT DESIGN COMPLIANCE. SHT.
 A-6.09 REFERS TO THE FAIR HOUSING ACT DESIGN MANUAL
 1998 BUT SHTS. A-6.10 AND A-8.00B REFER TO THE 1991
 FAIR HOUSING ACCESSIBILITY GUIDELINES. WHICH IS IT?
 CLARIFY.
 3) THE MEP RESPONSE NARRATIVE REFERS TO SHT. P-4.00.
 THERE IS NO SUCH DRAWING IN THE PLANS. IT APPEARS TO
 HAVE BEEN CHANGED TO P4.01. CLARIIFY.
 4) THE RESPONSE NARRATIVE PLAN REVIEW COMMENT #11
 REFERS TO DETAIL #3 FOR SINK/COUNTER ELEVATION FOR SINK
 AT THE POOL DECK. THERE IS NO DETAIL #3 ON SHT. A-5.07.
 CLARIFY.
 5) THE RESPONSE NARRATIVE FOR PLAN REVIEW COMMENT #13
 REFERS TO ELEVATIONS #13 & #14 ON SHT. A-5.05. THERE
 ARE NO SUCH ELEVVATIONS ON THIS SHEET. CLARIFY.
 6) SHT. A-2.00 - CLARIFY HOW PEOPLE IN THE GYM WILL
 HAVE UNRESTRICTED ACESS TO DRINKING FOUNTAINS IN THE
 YOGA AREA IN THE EVENT OF YOGA CLASSES.
 7)SHT.A-5.03 - DETAIL #4 - THERE SHALL BE A MINIMUM
 REQUIRED DEPTH OF 8 INCHES FOR KNEE CLEARANCE UNDER THE
 SINK AT 27 INCHES ABOVE THE FINISH FLOOR. ANSI
 A117.1-1986.
 8) SHT. A-5.04 - DETAILS #1 & #3 - LAVATORIES SHALL BE
 MOUNTED WITH A CLEARANCE OF AT LEAST 29 INCHES FROM THE
 FLOOR TO THE BOTTOM OF OF THE APRON PER ANSI
 A117.1-1986 . KNEE AND TOE CLEARANCES SHALL COMPLY WITH
 FIGURE 31 OF THE STANDARD.
 9) SHT. A-5.04 - DETAILS #2 & #3 - THE GRAB BARS ARE
 STILLL SHOWING THE MEASUREMENT TO THE CENTERLINE OF THE
 BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE.
 CLARIFY..
 10) SHT. A-5.05 - DETAILS #1, 2,3,4,5,8,9,10,11, &12 -
 THE GRAB BARS ARE ALL SHOWN MESURED TO THE CENTERLINE
 OF THE BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE.
 CLARIFY.
 11) SHT. A-5.06 - DETAIL #8 - THERE SHALL BE A MINIMUM
 REQUIRED DEPTH OF 8 INCHES FOR KNEE CLEARANCE UNDER THE
 SINK AT 27 INCHES ABOVE THE FINISH FLOOR. ANSI
 A117.1-1986.
 12) SHT. A-6.04 - DETAIL C - SHOW THE REQUIRED 30
 INCHES WIDE BY 48 INCHES DEEP CLEAR FLOOR SPACE OUTSIDE
 THE SWING OF THE DOOR PERR THE FAIR HOUSING ACT
 GUIDELINES/ DESIGN MANUAL.
 13) SHT. A-8.00A - COMMON AREAS FINISH SCHEDULE - SHOWS
 THE WALLS IN THE 3RD FLOOR RESTROOMS TO BE GYPSUM BOARD
 WITH WALL PAPER FINISH.WALLS AND PARTITIONS WITHIN TWO
 FEET OF WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LES THAN 4
 FEET ABOVE THE FLOOR AND THE MATERIALS USED IN SUCH
 WALLS SHALLL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. EPOXY PAINT DOES NOT MEET THIS
 REQUIREMENT.FBC-BUILDING SEC. 1210.2.2.
 14) - SHT. A-9.02 - DETAIL #9 REFERS TO DETAIL
 #12/A-9.02 - THERE IS NO DETAIL #12 ON THIS SHEET.
 CLARIFY.
 15) PLACE A NOTE ON THE PLANS THAT THE WASHING MACHINE
 SHUTOFF VALVES ARE ACCESSIBLE THROUGH A REMOVABLE PANEL
 ON THE WASHER/DRYER APPLIANCE . FBC-PLUMBING SEC.
 P606.3.
 16) SHT. P-1.00 - SHOW THE CONTINUATION POINT/
 ORIGINATION POINT OF THE FUTURE 1 1/4 INCH CONDENSATE
 DRAIN STUB OUT AT THE FUTURE RETAIL SPACE. THERE IS
 ANOTHER LINE NEXT TO THIS CONDENSATE LIINE THAT IS NOT
 IDENTIFIED OR SHOWS A PIPE SIZE. REFER TO COLUMN LINES
 A-B/3-4.
 17) SHT. P-1.00 - SHOW THE ONTINUATION POINT/
 ORIGINATION POINT OF THE 3 INCH CONDENSATE LINE
 DISCHARGING TO THE MANHOLE LOCATED AT COLUMN G//2-3..
 18) SHT. P-1.00 - SHOW THE CONTINUATION POINT OF THE 10
 INCH STORM DRAIN AND THE 1 1/4 INCH CONDENSATE LINE AT
 GRID LINE D-E/15.
 19) SHT.P-1.00- SIZE THE STORM, SANITARY, WATER LINES
 ON THE PLANS. PIPE SIZES ARE MISSING IN QUITE A FEW
 AREAS. WPB AMEND. TO FBC SEC. 107.2.1.
 20) SHT. P-1.01 - THERE ARE SANITARY RISER TAGS LOCATED
 AT COLUMNS D/2 WITH NO RISERS IDENTIED OR LOCATION
 ARROWS. REFER TO RISERS S/2, S/4, &S/6. CLARIFY.
 21) SHT. P-1.01 - THERE ARE RAINWATER AND OVERFLOW
 DRAIN RISER TAGS AT COLUMN LINES D/3-4 WITH NO RISERS
 SHOWN AND NO LOCATION ARROWS.ALSO, REFER TO COLUMN LINE
 C-D/5-6, C-D/9-10, C-D/7-8 FOR THE SAME ISSUE. CLARIFY.
 22) SHT. P-1.04 - THERE IS A RISER TAG OF RWL/5 LOCATED
 IN THE CORRIDOR AT COLUMNS D/7-8 BUT NO RISER IS SHOWN.
 THIS ALSO OCCURS IN UNIT C-2 IN THE HALL FOR RISER
 ODL/2. THE RWL/5 ISSUE ALSO OCCURS ON SHT.P-1.06.
 CLARIFY.
 23) P2.00 - UNIT B-1A - THERE IS A RISER TAG S/1C SHOWN
 AT THE STOVE AND THERE IS NO RISER. CLARIFY.
 24) SHT.P-1.03 - RISER TAGS ODL/3, RWL/3, S/2, ARE
 SHOWN IN THE CORRIDOR BUT THERE ARE NO CORRELATING
 RISERS SHOWN. CLARIFY.
 25) SHT. P-1.04 - RISER TAG RWL/5 IS SHOWN IN THE
 CORRIDOR BUT THERE IS NO CORRELATING RISER SHOWN.
 CLARIFY.
 26) SHT. P-1.05 - UNIT C-1A ACC. - RISER TAG RWL/1 IS
 SHOWN IN CORRIDOR BUT THERE IS NO CORRELATING RISER.
 CLARIFY.
 27) SHT.P-1.07 - THERE IS A RISER TAG OF RWL/5 LOCATED
 IN THE CORRIDOR AT COLUMNS D/7-8 BUT NO RISER IS SHOWN.
 CLARIFY.
 28) SHT.P-3.01 - UNIT B-1 - A SHUTOFF VALVE IS REQUIRED
 ON THE WATEER SUPPLY TO THE UNIT PER FBC-PLUMBING
 SEC.606.1.6.
 29) SHT. P-3.01- UNIT B-1A - A SHUTOFF VALVE IS
 REQUIRED ON THE WATEER SUPPLY TO THE UNIT PER
 FBC-PLUMBING SEC.606.1.6.
 30) SHT.P-3.02 - IDENTIFY THE PARTIAL GROUND FLOOR
 SANITARY PLAN AS THE OFFICE/ LOBBY AREA TO CORRELATE
 WITH SHT. P-2.02. WPB AMEND. O FBC SEC. 107.2.1.
 31) SHT. P-3.02 - THE BACKFLOW PREVENTION DEVICE AT THE
 POOL COLLECTOR TANK SHALL BE A REDUCED PRESSURE ZONE
 VALVE AND BE LEAD FREE. THE UNIT YOU HAVE SPECIFIED ON
 THE DRAWING IS A DOUBLE CHECK ASSEMBLY AND IS
 UNACCEPTABLE.FBC-PLUMBING TABLE 608.1.THE DEVICE SHALL
 COMPLY WITH ASSE 1013.
 32) SHT.P-3.04 - PLACE THE SLOPE OF THE HORIZONTAL
 STORM DRAIN PIPING ON THE PLAN. COMPLY WITH
 FBC-PLUMBING ABLE 1106.2.
 33) SHT. P-3.06 - SIZE ALL SECTIONS OF THE SANITARY
 COLLECTION SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 34) SHT. P-4.01 - FIXTURE CONNECTION SCHEDULE NOTE #1
 REFERS TO MIAMI-DADE CODE SECTION 8-31. DELETE THIS
 REFERENCE FROM THE NOTE.
 35) SHT. P-4.01- WATER HEATER DETAIL - SHOW THE SIZE OF
 THE EXPANSION TANK ON THE PLAN.
 36) SHT. P-4.01- TRASH CHUTE DETAIL- THE BACKFLOW
 DEVICE MUST BE LEAD FREE AND SHALL BE RELOCATED
 UPSTREAM OF THE SANITATION UNIT. AS PRESENTLY LOCATED,
 IT DOES NOT PROTECT THE BUILDING'S WATER SYSTEM.
 37) SUBMIT A COMPLETE WATER RISER FOR THE BUILDING. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 38) THE SUBMETERS SHALL BE NON COMBUSTIBLE IF LOCATED
 IN A RETURN AIR CLOSET AS IT APPEARS THEY ARE. THE
 SUBMITTED SPECS FOR THE METER DOES NOT SHOW THIS. HESE
 METERS ARE COMPOSED OF A POLYMER MATERIAL. RAPPING THE
 SUBMETERS WITH A FIRE WRAP IS NOT AN OPTION.
 39) SUBMIT ADDITIONAL INFORMATION/DETAILS ON THE
 BOOSTER PUMP. THE DETAIL ON SHT. P-4.01 IS VERY
 MINIMAL. WPB AMEND. TO FBC SEC. 107.2.1.2ND REQUEST.
 40) THE BACKFLOW PREVENTER FOR THE REFRIGERATOR DOES
 NOT COMPLY WITH THE ASSE 1022 STANDARD. ALL BACKFLOWS
 SHALL BE LEAD FREE. FBC-PLUMBING SEC.605.21.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW