Plan Review Notes
Plan Review Notes For Permit 20080364
Permit Number 20080364
Review Stop M
Sequence Number 2
Notes
Date Text
2020-10-09 15:59:352ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20080364
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO SHEET LS-1.01 THE WALLS SURROUNDING
 FCU-F AND FCU-A1 ARE 1-HOUR RATED WALLS. PLEASE SHOW
 THE REQUIRED FD AT EACH PENETRATION OF DUCTWORK. FBC M
 607.5
  
 2) PLEASE PROVIDE THE UL705 LISTING AND LABELING FOR
 THE CLOTHES DRYER EXHAUST DUCT POWER VENTILATORS. FBC M
 504.5
  
 3) THE LOUVER OF THE XVENT WILL RESTRICT THE EXHAUST
 FLOW OF THE DRYER. PLEASE PROVIDE A LETTER FROM THE
 MANUFACTURE OF THE DRYER STATING THAT THE DRYER WILL IN
 FACT WORK WITH THE XVENT. FBC M 504.8.4.2
  
 4) PLEASE PROVIDE SPECIFICATIONS FOR THE XVENT EXHAUST
 TERMINATION SHOWING THEY COMPLY WITH AMCA STANDARD 550
 . FBC M 501.3.2
  
 5) PLEASE PROVIDE SPECIFICATIONS FOR THE XVENT EXHAUST
 TERMINATION INDICATING THE OPENINGS AT THE TERMINATION
 FACE MEETS THE SIZES REQUIRED IN FBC M 501.3.2 (MINIMUM
 ?? AND NOT LARGER THAN ??)
  
 6) KEYNOTE (8) REQUIRES A NON-CORROSIVE BIRD SCREEN AT
 THE TERMINATION LOCATION FOR ALL THE BATH EXHAUST
 DUCTS. THE INFORMATION PROVIDED ON THE XVENT WEBSITE
 DOES NOT SHOW A BIRD SCREEN. PLEASE PROVIDE INFORMATION
 AND INSTALLATION INSTRUCTIONS FOR THIS SCREEN. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  