| 2020-08-24 10:36:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | THE FOLLOWING SYSTEMS SHALL PER PERMITTED SEPARATELY |
| | BDA, FIRE ALARM, GENERATOR, SITE LIGHTING, POOL, AND |
| | LOW VOLTAGE DATA, TELEPHONE. CCTV, AND TV, IF THESE |
| | SYSTEMS ARE INCLUDED WITH THE GENERAL PERMIT YOU WILL |
| | BE REQUIRED TO GIVE THE CITY A BREAKDOWN OF THE COSTS |
| | OF THESE SYSTEMS FOR PERMITTING PURPOSES. |
| | |
| | |
| | |
| | PAGE E-4.02 |
| | |
| | 1) ARC ENERGY REDUCTION SHALL BE PROVIDED PER 240.87. |
| | 240.87 ARC ENERGY REDUCTION WHERE THE HIGHEST |
| | CONTINUOUS CURRENT TRIP SETTING FOR WHICH THE ACTUAL |
| | OVERCURRENT DEVICE INSTALLED IN A CIRCUIT BREAKER IS |
| | RATED OR CAN BE ADJUSTED IS 1200 A OR HIGHER |
| | |
| | 2) FAULT CURRENT CALCULATION AND LABELS ARE REQUIRED BY |
| | SECTIONS 110.9, 110,10, 110.24 |
| | |
| | 3) WIRE SIZES ARE NOT SHOWN FOR THE MAINS FROM THE |
| | VAULT. |
| | |
| | 4) WIRE SIZES FROM THE GENERATOR TO THE ATS ARE NOT |
| | SHOWN. NO CONDUCTORS ARE SHOWN ON THE LOAD SIDE OF THE |
| | ATS. |
| | |
| | 5) RISER DOES NOT SHOW WHAT IS BEING FED BY THE ATS. |
| | |
| | 6) GENERATOR ROOM SHOWS YOGA AND STAIR TOWER #2 |
| | |
| | 7) MAIN #4 IS IT 400A OR 800A RISER SHOWS TWO DIFFERENT |
| | SIZES. |
| | |
| | PAGE E-500 |
| | |
| | LEGEND GENERAL NOTES #3 WHICH SHOULD BE #4 DOES NOT |
| | INCLUDE KITCHEN AND LAUNDRY AREAS FOR ARC FAULTS. |
| | GENERAL ELECTRICAL NOTES #1 NEED FAULT CURRENT RATING |
| | OF THE MAINS AND SUBPANELS 110.9, 110.10, AND PROVIDE |
| | SIGN PER 110.24 |
| | GENERAL ELECTRICAL NOTES #5 STATES CITY OF FT |
| | LAUDERDALE AND 68 DB NEED TO CHECK WITH THE CITY OF WPB |
| | ZONING CODE. |