| 2020-10-15 07:47:58 | NEW 8 STORY BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE 2ND FLOOR |
| | RETAIL NUMBER 1 SPACE (STAIRS ARE NOT A COMPONENT OF AN |
| | ACCESSIBLE ROUTE FBC A 402.2) FBC A 201.1.1 VERTICAL |
| | ACCESSIBILITY. |
| | 2) PLEASE SHOW THE REQUIRED STAIR HANDRAILS FOR THE 2ND |
| | FLOOR RETAIL SPACE NUMBER 1 TO COMPLY WITH FBC 1011.11 |
| | 3) PLEASE SHOW THE DETAILS FOR THE ADDED EGRESS |
| | STAIRWAY ON THE REVISED POOL DECK DRAWING TO COMPLY |
| | WITH FBC CHAPTER 10 |
| | 4) CANNOT HAVE OPENINGS ON THE NORTH WALL 1ST AND 2ND |
| | FLOOR AND ONLY 15% FOR THE REMAINING FLOORS PER FBC |
| | 705.8.2 (UNLESS YOU CAN SHOW THAT THE AREA NORTH OF THE |
| | PROPERTY LINE MEETS THE EXCEPTIONS OF FBC 705.8.1). |
| | 5) DRAWING REVISIONS IN PROJECTDOX NEED TO BE ADDED TO |
| | ?DRAWINGS? FOLDER NOT ?SUPPORTING DOCS? FOLDER. CONTACT |
| | [email protected] FOR ASSISTANCE. |
| | 6) REVISED DRAWING (A-3.08) UNPROTECTED OPENINGS EAST |
| | SIDE ? HASH MARKS ON THE EAST SIDE ARE FOR UNPROTECTED |
| | OPENINGS? ? THE RETAIL AREA 2 GLAZING IS NOT SHOWN AS |
| | FIRE RATED ? EXIT DOOR (C17) IS NOT SHOWN AS FIRE RATED |
| | - PLEASE REVISE THE OPENING PROTECTION CALCULATIONS. |
| | 7) EXIT SPACING SHOWN ON THE 3RD FLOOR POOL DECK IS NOT |
| | ? OR MORE THAN THE DIAGONAL DISTANCE SHOWN ? FBC |
| | 1007.1.1 |
| | 8) PLEASE FILL OUT THE REQUIRED THRESHOLD FORMS ? |
| | ?THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF |
| | UNDERSTANDING? ? SEE THE ?GUIDELINES AND POLICIES FOR |
| | PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND |
| | RESIDENT INSPECTORS? ? WHICH CAN BE PROVIDED BY E |
| | MAILING [email protected] AND ASKING FOR THE THRESHOLD |
| | GUIDELINES BROCHURE. |
| | |
| | DEFERRED ITEMS ? TO BE REVIEWED AND MARKED APPROVED BY |
| | THE BUILDING DESIGNER OF RECORD AND REVIEWED BY THE |
| | BUILDING DIVISION PLAN REVIEW BEFORE INSTALLATION - |
| | 1) EXTERIOR WINDOW, DOOR AND LOUVER PRODUCT APPROVALS. |
| | FBC 1609 |
| | 2) SHORING AND RESHORING PLANS. FBC 110.8.4.3 |
| | 3) GUARD RAILING. FBC 1607.8 |
| | 4) ROOFING SYSTEM PRODUCT APPROVALS. FBC 1609.5.2 |
| | 5) ROOF TOP EQUIPMENT SCREENING. FBC 1510.6 |
| | 6) POOL. FBC 454 |
| | 7) ACOUSTICAL TEST REPORTS FOR THE FLOOR/CEILING |
| | ASSEMBLIES IIC AND STC PER FBC 1207 AND FLAME SPREAD |
| | INDEX PER FBC 603.1 |
| | |
| | |