Plan Review Notes
Plan Review Notes For Permit 20080364
Permit Number 20080364
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-15 07:47:58NEW 8 STORY BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE 2ND FLOOR
 RETAIL NUMBER 1 SPACE (STAIRS ARE NOT A COMPONENT OF AN
 ACCESSIBLE ROUTE FBC A 402.2) FBC A 201.1.1 VERTICAL
 ACCESSIBILITY.
 2) PLEASE SHOW THE REQUIRED STAIR HANDRAILS FOR THE 2ND
 FLOOR RETAIL SPACE NUMBER 1 TO COMPLY WITH FBC 1011.11
 3) PLEASE SHOW THE DETAILS FOR THE ADDED EGRESS
 STAIRWAY ON THE REVISED POOL DECK DRAWING TO COMPLY
 WITH FBC CHAPTER 10
 4) CANNOT HAVE OPENINGS ON THE NORTH WALL 1ST AND 2ND
 FLOOR AND ONLY 15% FOR THE REMAINING FLOORS PER FBC
 705.8.2 (UNLESS YOU CAN SHOW THAT THE AREA NORTH OF THE
 PROPERTY LINE MEETS THE EXCEPTIONS OF FBC 705.8.1).
 5) DRAWING REVISIONS IN PROJECTDOX NEED TO BE ADDED TO
 ?DRAWINGS? FOLDER NOT ?SUPPORTING DOCS? FOLDER. CONTACT
 [email protected] FOR ASSISTANCE.
 6) REVISED DRAWING (A-3.08) UNPROTECTED OPENINGS EAST
 SIDE ? HASH MARKS ON THE EAST SIDE ARE FOR UNPROTECTED
 OPENINGS? ? THE RETAIL AREA 2 GLAZING IS NOT SHOWN AS
 FIRE RATED ? EXIT DOOR (C17) IS NOT SHOWN AS FIRE RATED
 - PLEASE REVISE THE OPENING PROTECTION CALCULATIONS.
 7) EXIT SPACING SHOWN ON THE 3RD FLOOR POOL DECK IS NOT
 ? OR MORE THAN THE DIAGONAL DISTANCE SHOWN ? FBC
 1007.1.1
 8) PLEASE FILL OUT THE REQUIRED THRESHOLD FORMS ?
 ?THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF
 UNDERSTANDING? ? SEE THE ?GUIDELINES AND POLICIES FOR
 PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND
 RESIDENT INSPECTORS? ? WHICH CAN BE PROVIDED BY E
 MAILING [email protected] AND ASKING FOR THE THRESHOLD
 GUIDELINES BROCHURE.
  
 DEFERRED ITEMS ? TO BE REVIEWED AND MARKED APPROVED BY
 THE BUILDING DESIGNER OF RECORD AND REVIEWED BY THE
 BUILDING DIVISION PLAN REVIEW BEFORE INSTALLATION -
 1) EXTERIOR WINDOW, DOOR AND LOUVER PRODUCT APPROVALS.
 FBC 1609
 2) SHORING AND RESHORING PLANS. FBC 110.8.4.3
 3) GUARD RAILING. FBC 1607.8
 4) ROOFING SYSTEM PRODUCT APPROVALS. FBC 1609.5.2
 5) ROOF TOP EQUIPMENT SCREENING. FBC 1510.6
 6) POOL. FBC 454
 7) ACOUSTICAL TEST REPORTS FOR THE FLOOR/CEILING
 ASSEMBLIES IIC AND STC PER FBC 1207 AND FLAME SPREAD
 INDEX PER FBC 603.1
  
  