| 2020-08-25 07:39:20 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20080364 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1.00: UNIT FCU-N WILL BE REVIEWED AT TIME OF |
| | RETAIL SPACE UPFIT. FBC FS 107.2.1 |
| | |
| | 2) SHEET M-1.00: UNIT FCU-O WILL BE REVIEWED AT TIME OF |
| | RETAIL SPACE UPFIT. FBC FS 107.2.1 |
| | |
| | 3) SHEET M-1.00: PLEASE PROVIDE O.A. CALCULATIONS FOR |
| | THE LOADING VESTIBULE AND THE BIKE STORAGE ROOM. FBC M |
| | 401.2,401.3 |
| | |
| | 4) SHEET M-1.00: WHAT AREA DOES FCU-A2 SERVE? I DO NOT |
| | SEE ANY DUCT WORK FOR THIS UNIT. FBC FS 107.2.1 |
| | |
| | 5) SHEET M-1.00: PLEASE SHOW HOW YOU ARE BRINGING IN |
| | O.A. TO UNIT FCU-A2. FBC FS 107.2.1 |
| | |
| | 6) SHEET M-1.01: PLEASE PROVIDE FIRE DAMPERS WHERE THE |
| | RATED WALL IS PENETRATED BY THE MECHANICAL SYSTEM |
| | DUCTS. FBC FS 107.2.1 |
| | |
| | 7) SHEET M-1.01: PLEASE PROVIDE VENTILATION |
| | CALCULATIONS FOR THE BIKE STORAGE AND SHOW HOW YOU ARE |
| | BRINGING IN O.A. TO THIS AREA AND TENANT STORAGE. FBC M |
| | 401.2,401.3 |
| | |
| | 8) SHEET M-1.01: PLEASE SHOW HOW YOU ARE BRINGING O.A. |
| | INTO FCU-A1 AND FCU-F. FBC M 401.2, 401.3 |
| | |
| | 9) SHEET M-1.01: PLEASE PROVIDE O.A. TO THE MAINTENANCE |
| | ROOMS. FBC M 401.2, 401.3 |
| | |
| | 10) INDIVIDUAL UNIT PLANS: PLEASE SHOW ALL DRYER DUCTS |
| | CONTINUOUS TO THE EXTERIOR TERMINATIONS. FBC FS 107.2.1 |
| | |
| | 11) SHEET M-2.00: PLEASE SHOW A DETAIL DRAWING OF THE |
| | RETURN FROM BEDROOM IN UNIT A-1. FBC FS 107.2.1 |
| | |
| | 12) SHEET M-2.00: PLEASE INDICATE THE RATED DOOR FOR |
| | THE MECHANICAL CLOSET FOR UNIT A-1A. FBC FS 107.2.1 |
| | |
| | 13) SHEET M-2.00: PLEASE SHOW A DETAIL OF THE RETURN IN |
| | THE BEDROOM FOR UNIT A-1A. FBC FS 107.2.1 |
| | |
| | 14) SHEET M-2.00: (NOTE 10) PLEASE PROVIDE INFORMATION |
| | ON THIS DRYER BOX. IT APPEARS THAT SOME ARE INSTALLED |
| | INSIDE OF A RATED WALL, THE DRYER BOX WOULD NEED TO BE |
| | RATED IN THIS LOCATION. FBC FS 107.2.1 |
| | |
| | 15) SHEET M-2.00: PLEASE CHECK THE NUMBER OF BENDS IN |
| | THE DRYER DUCT FOR UNIT B-1. FBC FS 107.2.1 |
| | |
| | 16) SHEET M-2.02: PLEASE SHOW THE RETURN AIR PATH BACK |
| | TO FCU-B THROUGH THE RATED WALL OF THE MECHANICAL ROOM. |
| | FBC FS 107.2.1 |
| | |
| | 17) SHEET M-2.02: PLEASE PROVIDE A DETAIL OF THE AREA |
| | AT THE 24X10 R>A> BOXES ARE LOCATED. FBC FS 107.2.1 |
| | |
| | 18) SHEET M-2.02: PLEASE PROVIDE SPECS ON SHEET M-3.01 |
| | FOR TF-1 AND TF-2. FBC FS 107.2.1 |
| | |
| | 19) SHEET M-2.03: PLEASE CONTINUE R.A. DUCT WORK FROM |
| | FCU-A1 SHOWING THE FIRE DAMPERS AT DUCTWORK PENETRATING |
| | RATED WALLS. FBC FS 107.2.1 |
| | |
| | 20) SHEET M-2.03: PLEASE SHOW FIRE DAMPERS IN DUCTS |
| | THAT PENETRATE ALL RATED WALLS. FBC FS 107.2.1 |
| | |
| | 21) SHEET M-2.03 PLEASE SHOW HOW YOU ARE BRINGING O.A. |
| | INTO FCU-H. FBC M 401.2, 401.3 |
| | |
| | 22) SHEET M-2.03: PLEASE SHOW HOW YOU ARE BRINGING O.A. |
| | INTO FCU-I. FBC M 401.2, 401.3 |
| | |
| | 23) SHEET M-3.01: ( OUTDOOR AIR CALCULATIONS) PLEASE |
| | REFERENCE THE CURRENT EDITION OF THE MECHANICAL CODE. |
| | 2017 FLORIDA BUILDING CODE MECHANICAL CODE |
| | |
| | 24) SHEET M-5.01: PLEASE SHOW HOW THE X-VENT MEETS |
| | SECTION 504.4 OF FBC M FOR NO SCREENS AT THE |
| | TERMINATION OF A DRYER DUCT. |
| | |
| | 25) SHEET M-5.01: PLEASE INDICATE ON THE UNIT DRAWINGS |
| | WHEN THE TOILET EXHAUST MULTIPLE CONNECTION IS USED. |
| | FBC FS 107.2.1 |
| | |
| | 26) SHEETS M-1.02- M-1.07: PLEASE CHECK THE CORRIDOR |
| | CFMS. MY NUMBERS ARE: 3RD FLOOR= 90 CFM; 4TH ? 8TH EACH |
| | HAS 1010 CFM?S. DRAWINGS INDICATE: NO INDICATION FOR |
| | 3RD FLOOR; 4TH -8TH DRAWINGS INDICATE 1370 CFM?S. FBC |
| | FS 107.2.1 |
| | |
| | 27) SHEET M-2.02: PLEASE SHOW DETAIL OF 8? O/A DUCT FOR |
| | FCU-A2 MECHANICAL CLOSET. NOTE INDICATES ITS ON SHEET |
| | M- 2.03. IT DOES NOT APPEAR TO BE ON THAT SHEET. FBC FS |
| | 107.2.1 |
| | |
| | 28) SHEET M-2.02: PLEASE SHOW WHERE BATH EXHAUST |
| | TERMINATES FOR MALE AND FEMALE BATHROOMS BY THE MAIL |
| | ROOM. IDENTIFY WHICH EXHAUST FAN IS BEING USED. TEF-1 |
| | HAS A TOTAL OF 300CFM. THE BATHROOMS IN THE GYM |
| | INDICATE THIS IS THE EXHAUST FAN BEING USED. PLEASE |
| | VERIFY THIS. FBC FS 107.2.1 |
| | |
| | 29) SHEET M-4.01: THE CORRIDOR SUPPLY RISER NUMBERS DO |
| | NOT MATCH CFM?S ON SHEETS M-1.02- M-1.07, PLEASE BE |
| | CONSISTENT. FBC FS 107.2.1 |
| | |
| | 30) SHEET M-5.03: THE RUSKIN LOUVER DETAIL DOES NOT |
| | INDICATE THE SIZE OF THIS LOUVER, PLEASE COMPLETE THE |
| | SIZE OF THIS LOUVER. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |