Plan Review Notes
Plan Review Notes For Permit 20080364
Permit Number 20080364
Review Stop M
Sequence Number 1
Notes
Date Text
2020-08-25 07:39:201ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080364
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.00: UNIT FCU-N WILL BE REVIEWED AT TIME OF
 RETAIL SPACE UPFIT. FBC FS 107.2.1
  
 2) SHEET M-1.00: UNIT FCU-O WILL BE REVIEWED AT TIME OF
 RETAIL SPACE UPFIT. FBC FS 107.2.1
  
 3) SHEET M-1.00: PLEASE PROVIDE O.A. CALCULATIONS FOR
 THE LOADING VESTIBULE AND THE BIKE STORAGE ROOM. FBC M
 401.2,401.3
  
 4) SHEET M-1.00: WHAT AREA DOES FCU-A2 SERVE? I DO NOT
 SEE ANY DUCT WORK FOR THIS UNIT. FBC FS 107.2.1
  
 5) SHEET M-1.00: PLEASE SHOW HOW YOU ARE BRINGING IN
 O.A. TO UNIT FCU-A2. FBC FS 107.2.1
  
 6) SHEET M-1.01: PLEASE PROVIDE FIRE DAMPERS WHERE THE
 RATED WALL IS PENETRATED BY THE MECHANICAL SYSTEM
 DUCTS. FBC FS 107.2.1
  
 7) SHEET M-1.01: PLEASE PROVIDE VENTILATION
 CALCULATIONS FOR THE BIKE STORAGE AND SHOW HOW YOU ARE
 BRINGING IN O.A. TO THIS AREA AND TENANT STORAGE. FBC M
 401.2,401.3
  
 8) SHEET M-1.01: PLEASE SHOW HOW YOU ARE BRINGING O.A.
 INTO FCU-A1 AND FCU-F. FBC M 401.2, 401.3
  
 9) SHEET M-1.01: PLEASE PROVIDE O.A. TO THE MAINTENANCE
 ROOMS. FBC M 401.2, 401.3
  
 10) INDIVIDUAL UNIT PLANS: PLEASE SHOW ALL DRYER DUCTS
 CONTINUOUS TO THE EXTERIOR TERMINATIONS. FBC FS 107.2.1
  
 11) SHEET M-2.00: PLEASE SHOW A DETAIL DRAWING OF THE
 RETURN FROM BEDROOM IN UNIT A-1. FBC FS 107.2.1
  
 12) SHEET M-2.00: PLEASE INDICATE THE RATED DOOR FOR
 THE MECHANICAL CLOSET FOR UNIT A-1A. FBC FS 107.2.1
  
 13) SHEET M-2.00: PLEASE SHOW A DETAIL OF THE RETURN IN
 THE BEDROOM FOR UNIT A-1A. FBC FS 107.2.1
  
 14) SHEET M-2.00: (NOTE 10) PLEASE PROVIDE INFORMATION
 ON THIS DRYER BOX. IT APPEARS THAT SOME ARE INSTALLED
 INSIDE OF A RATED WALL, THE DRYER BOX WOULD NEED TO BE
 RATED IN THIS LOCATION. FBC FS 107.2.1
  
 15) SHEET M-2.00: PLEASE CHECK THE NUMBER OF BENDS IN
 THE DRYER DUCT FOR UNIT B-1. FBC FS 107.2.1
  
 16) SHEET M-2.02: PLEASE SHOW THE RETURN AIR PATH BACK
 TO FCU-B THROUGH THE RATED WALL OF THE MECHANICAL ROOM.
 FBC FS 107.2.1
  
 17) SHEET M-2.02: PLEASE PROVIDE A DETAIL OF THE AREA
 AT THE 24X10 R>A> BOXES ARE LOCATED. FBC FS 107.2.1
  
 18) SHEET M-2.02: PLEASE PROVIDE SPECS ON SHEET M-3.01
 FOR TF-1 AND TF-2. FBC FS 107.2.1
  
 19) SHEET M-2.03: PLEASE CONTINUE R.A. DUCT WORK FROM
 FCU-A1 SHOWING THE FIRE DAMPERS AT DUCTWORK PENETRATING
 RATED WALLS. FBC FS 107.2.1
  
 20) SHEET M-2.03: PLEASE SHOW FIRE DAMPERS IN DUCTS
 THAT PENETRATE ALL RATED WALLS. FBC FS 107.2.1
  
 21) SHEET M-2.03 PLEASE SHOW HOW YOU ARE BRINGING O.A.
 INTO FCU-H. FBC M 401.2, 401.3
  
 22) SHEET M-2.03: PLEASE SHOW HOW YOU ARE BRINGING O.A.
 INTO FCU-I. FBC M 401.2, 401.3
  
 23) SHEET M-3.01: ( OUTDOOR AIR CALCULATIONS) PLEASE
 REFERENCE THE CURRENT EDITION OF THE MECHANICAL CODE.
 2017 FLORIDA BUILDING CODE MECHANICAL CODE
  
 24) SHEET M-5.01: PLEASE SHOW HOW THE X-VENT MEETS
 SECTION 504.4 OF FBC M FOR NO SCREENS AT THE
 TERMINATION OF A DRYER DUCT.
  
 25) SHEET M-5.01: PLEASE INDICATE ON THE UNIT DRAWINGS
 WHEN THE TOILET EXHAUST MULTIPLE CONNECTION IS USED.
 FBC FS 107.2.1
  
 26) SHEETS M-1.02- M-1.07: PLEASE CHECK THE CORRIDOR
 CFMS. MY NUMBERS ARE: 3RD FLOOR= 90 CFM; 4TH ? 8TH EACH
 HAS 1010 CFM?S. DRAWINGS INDICATE: NO INDICATION FOR
 3RD FLOOR; 4TH -8TH DRAWINGS INDICATE 1370 CFM?S. FBC
 FS 107.2.1
  
 27) SHEET M-2.02: PLEASE SHOW DETAIL OF 8? O/A DUCT FOR
 FCU-A2 MECHANICAL CLOSET. NOTE INDICATES ITS ON SHEET
 M- 2.03. IT DOES NOT APPEAR TO BE ON THAT SHEET. FBC FS
 107.2.1
  
 28) SHEET M-2.02: PLEASE SHOW WHERE BATH EXHAUST
 TERMINATES FOR MALE AND FEMALE BATHROOMS BY THE MAIL
 ROOM. IDENTIFY WHICH EXHAUST FAN IS BEING USED. TEF-1
 HAS A TOTAL OF 300CFM. THE BATHROOMS IN THE GYM
 INDICATE THIS IS THE EXHAUST FAN BEING USED. PLEASE
 VERIFY THIS. FBC FS 107.2.1
  
 29) SHEET M-4.01: THE CORRIDOR SUPPLY RISER NUMBERS DO
 NOT MATCH CFM?S ON SHEETS M-1.02- M-1.07, PLEASE BE
 CONSISTENT. FBC FS 107.2.1
  
 30) SHEET M-5.03: THE RUSKIN LOUVER DETAIL DOES NOT
 INDICATE THE SIZE OF THIS LOUVER, PLEASE COMPLETE THE
 SIZE OF THIS LOUVER. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  