| 2020-08-26 14:25:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1)SHEET A 2.02 & LS 1.02 - THE DOUBLE COMMUNITY ROOM |
| | DOORS OPEN INTO AN EXIT CORRIDOR: |
| | |
| | THERE IS NO DIMENSION INDICATING COMPLIANCE WITH THE |
| | RESTRICTED EGRESS WIDTH CODE: |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE REVIEW AND PROVIDE A COMPLIANT WIDTH DIMENSION. |
| | |
| | |
| | |
| | 2) SHEET A 8.00 - UNDER THE NOTE SECTION # 22 THERE IS |
| | REFERENCE TO ACCESS CONTROL. |
| | |
| | ANY PROPOSED ACCESS CONTROL SHALL COMPLY WITH THE |
| | APPLICABLE SECTION OF NFPA 101 AND BE SUBMITTED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A CLOUDED NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 3) SHEET A 8.00 - UNDER THE NOTE SECTION # 12 THERE IS |
| | REFERENCE TO NFPA 101 7.2.1.5.7. |
| | |
| | THIS REFERENCE DOES NOT APPEAR TO BE CORRECT: |
| | |
| | 7.2.1.5.7 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| | KEY |
| | OPERATION SHALL BE PERMITTED, PROVIDED THAT THE KEY |
| | CANNOT BE |
| | REMOVED WHEN THE DOOR LEAF IS LOCKED FROM THE SIDE FROM |
| | WHICH |
| | EGRESS IS TO BE MADE. |
| | |
| | PLEASE REVIEW AND PROVIDE A CLOUDED CORRECTED CODE |
| | REFERENCE OR REMOVE. |
| | |
| | |
| | |
| | 4) SHEET FA 1.00 & 2.00 - THERE ARE NUMEROUS |
| | INDICATIONS OF PULL STATIONS AT EACH EXIT. |
| | |
| | IN AN EFFORT TO REDUCE FALSE ALARMS NFPA 101 ALLOWS THE |
| | REDUCTION OF PULL STATIONS IN OCCUPANCIES WITH FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | NFPA 101, CH 30, NEW APARTMENT OCCUPANCIES |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR |
| | WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE |
| | MEETING THE |
| | REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A |
| | FIRE ALARM |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS |
| | MODIFIED BY |
| | 30.3.4.2 THROUGH 30.3.4.5. |
| | |
| | 30.3.4.2 INITIATION. |
| | 30.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY |
| | MANUAL MEANS IN ACCORDANCE WITH 9.6.2, UNLESS THE |
| | BUILDING |
| | COMPLIES WITH 30.3.4.2.2. |
| | |
| | 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON |
| | OPERATION OF |
| | THE AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | NFPA 101 CH 9, BUILDING SERVICE AND FIRE PROTECTION |
| | EQUIPMENT |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | 9.6.2.8 WHERE A SPRINKLER SYSTEM PROVIDES AUTOMATIC |
| | DETECTION |
| | AND ALARM SYSTEM INITIATION, IT SHALL BE PROVIDED WITH |
| | AN APPROVED |
| | ALARM INITIATION DEVICE THAT OPERATES WHEN THE FLOW OF |
| | WATER IS |
| | EQUAL TO OR GREATER THAN THAT FROM A SINGLE AUTOMATIC |
| | SPRINKLER. |
| | |
| | PLEASE REVIEW AND, IF DESIRED AND AGREED BY THE EOR, |
| | PROVIDE A CLOUDED NOTE OF ACKNOWLDGEMENT TO COORDINATE |
| | PULL STATION LOCATIONS WITH THE OFFICE OF THE FIRE |
| | MARSHAL |
| | |
| | |
| | 5) SHEET FA 1.00 & 2.00 - THERE ARE NUMEROUS |
| | INDICATIONS OF SMOKE DECTECTORS THROUGHT COMMON AREAS |
| | AND CERTAIN ROOMS. |
| | |
| | IN AN EFFORT TO REDUCE FALSE ALARMS NFPA 101 ALLOWS FOR |
| | THE REDUCTION OF SOKE DETECTION IN OCCUPANCIES WHERE |
| | TOTAL DETECTION SI NOT REQUIRED. |
| | |
| | NFPA 101, CH 30, NEW APARTMENT OCCUPANCIES |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR |
| | WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE |
| | MEETING THE |
| | REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A |
| | FIRE ALARM |
| | SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS |
| | MODIFIED BY |
| | 30.3.4.2 THROUGH 30.3.4.5. |
| | |
| | 30.3.4.2 INITIATION. |
| | 30.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY |
| | MANUAL MEANS IN ACCORDANCE WITH 9.6.2, UNLESS THE |
| | BUILDING |
| | COMPLIES WITH 30.3.4.2.2. |
| | |
| | 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 30.3.5, |
| | REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON |
| | OPERATION OF |
| | THE AUTOMATIC SPRINKLER SYSTEM. |
| | |
| | NFPA 101 CH 9, BUILDING SERVICE AND FIRE PROTECTION |
| | EQUIPMENT |
| | |
| | 9.6.2.9 WHERE A TOTAL (COMPLETE) COVERAGE SMOKE |
| | DETECTION |
| | SYSTEM IS REQUIRED BY ANOTHER SECTION OF THIS CODE, |
| | AUTOMATIC |
| | DETECTION OF SMOKE IN ACCORDANCE WITH NFPA 72, NATIONAL |
| | FIRE |
| | ALARM AND SIGNALING CODE, SHALL BE PROVIDED IN ALL |
| | OCCUPIABLE |
| | AREAS IN ENVIRONMENTS THAT ARE SUITABLE FOR PROPER |
| | SMOKE DETECTOR |
| | OPERATION. |
| | |
| | SMOKE DETECTION IS NOT SPECIFICALLY REQUIRED THROUGHT |
| | THE BUILDING. |
| | |
| | PLEASE REVIEW AND, IF DESIRED AND AGREED BY THE EOR, |
| | PROVIDE A CLOUDED NOTE OF ACKNOWLDGEMENT TO COORDINATE |
| | ONLY REQUIRED SMOKE DETECTIONS LOCATIONS WITH THE |
| | OFFICE OF THE FIRE MARSHAL. |
| | |
| | |
| | 6) SHEET 2.00 - UNDER SEQUENCE OF OPERATION # 3 THERE |
| | IS AN INDICATION OF DUCT DETECTION SENDING A TROUBLE |
| | SIGNAL. |
| | |
| | PER NFPA 90A, 2015 ED. |
| | |
| | 6.4.3* FUNCTION. |
| | 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 |
| | SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON |
| | DETECTING THE PRESENCE OF SMOKE. |
| | |
| | 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE |
| | AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A |
| | BUILDING, THE SMOKE DETECTORS REQUIRED BY THE |
| | PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE |
| | FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS |
| | OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING |
| | CODE. |
| | |
| | 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING |
| | DAMPERS OR FOR HEATING, VENTILATING, AND |
| | AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED |
| | TO ACTIVATE THE BUILDING EVACUATION ALARM. |
| | |
| | PER NFPA 72, 2013 ED |
| | |
| | 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS. |
| | 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO |
| | BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS |
| | INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET |
| | THE REQUIREMENTS OF 21.7.4. |
| | 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC |
| | SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. |
| | 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| | HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A |
| | CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION |
| | SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL. |
| | 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| | HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM |
| | SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES, |
| | OR STANDARDS. |
| | |
| | PLEASE REVIEW AND CORRECT WITH AN APPLICABLE CLOUDED |
| | NOTE. |
| | |
| | |
| | 7) SHEET FA 2.00 - THE FIRE ALARM SHALL BE INSTALLED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY A CERTIFIED |
| | FIRE ALARM CONTRCTOR. |
| | |
| | PLEASE REVIEW AND CORRECT WITH AN APPLICABLE CLOUDED |
| | NOTE. |
| | |
| | |
| | |
| | 8) SHEET FA 2.00 - THE FIRE ALARM SYSTEM SHALL BE |
| | INSTALLED UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY A |
| | CERTIFIED FIRE ALARM CONTRACTOR. |
| | |
| | PLEASE REVIEW AND CORRECT WITH AN APPLICABLE CLOUDED |
| | NOTE. |
| | |
| | |
| | 9) SHEET FP 1.00 - THE FIRE SPRINKLER SYSTEM SHALL BE |
| | INSTALLED UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY A |
| | CERTIFIED FIRE SPRINKLER CONTRACTOR. |
| | |
| | PLEASE REVIEW AND CORRECT WITH AN APPLICABLE CLOUDED |
| | NOTE. |
| | |
| | |
| | 10) SHEET FP 1.00 & C 9 - THE FIRE LINE UNDERGROUND |
| | SYSTEM INCLUDING THE DDCV SHALL BE INSTALLED UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS BY A CERTIFIED FIRE |
| | LINE UNDERGROUND CONTRACTOR IN COMPLIANCE WITH NFPA 24. |
| | |
| | PLEASE REVIEW AND CORRECT WITH AN APPLICABLE CLOUDED |
| | NOTE. |
| | |
| | |
| | 11)SHEET A 0.03 - GENERAL INFO - REQUIRED RADIO |
| | COMMUNICATION SYSTEM. |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | 11.10.2 WHERE REQUIRED BY THE AHJ, TWO-WAY RADIO |
| | COMMUNICATION |
| | ENHANCEMENT SYSTEMS SHALL COMPLY WITH NFPA 72. |
| | |
| | NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS |
| | ENHANCEMENT SYSTEMS. |
| | |
| | 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE |
| | PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF |
| | FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH |
| | 24.5.2.2.3. |
| | 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE |
| | EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S), |
| | EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES, |
| | STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE |
| | LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE |
| | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH |
| | 99 PERCENT FLOOR AREA RADIO COVERAGE. |
| | 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING |
| | AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA |
| | RADIO COVERAGE. |
| | 24.5.2.3 SIGNAL STRENGTH. |
| | 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH |
| | OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED |
| | THROUGHOUT THE COVERAGE AREA. |
| | 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH |
| | OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH |
| | AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL |
| | BE PROVIDED FROM THE COVERAGE AREA. |
| | |
| | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST |
| | PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN |
| | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES |
| | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE |
| | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| | SAFETY RADIO SYSTEMS MANAGER, AS OUR RADIOS OPERATE ON |
| | THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | PLEASE REVIEW AND CORRECT WITH AN APPLICABLE CLOUDED |
| | NOTE. |
| | |
| | |
| | |
| | 12) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 13) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |