| 2020-09-03 10:38:00 | PLAN |
| | REVIEW COMMENTS |
| | THRESHOLD BUILDING |
| | 8 STORY APARTMENT BUILDING (MIXED USE R-2, M, S-2 ) |
| | CONST. TYPE 1-B, SPRINKLERED |
| | 170 MPH, EXPOSURE "C" |
| | FLOOD ZONE "X" |
| | 951 BANYAN |
| | PERMIT #20080364 |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THIS IS A THRESHOLD BUILDING / FL S. S. 553.71(7). |
| | "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| | BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER |
| | 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. |
| | |
| | 2) SUBMIT MANAGEMENT OF TRAFFIC (MOT) PLANS AND SPECIFY |
| | HOW COMPLIANCE WITH FBC CHAPTER 33 SAFEGUARDS DURING |
| | CONSTRUCTION FOR THE FOUNDATION PERMIT WILL BE MET. |
| | |
| | 3) THE PROJECT APPEARS TO ENCOMPASS SEVERAL PARCELS OR |
| | LOTS. A UNITY OF TITLE WILL BE REQUIRED BEFORE THE |
| | PERMIT IS ISSUED. FBC 107.2.1 |
| | |
| | 4) SUBMIT A GEOTECHNICAL REPORT THAT SPECIFIES THE |
| | REQUIRED SOIL BEARING CAPACITY AND THE RECOMMENDED SOIL |
| | PREPARATION METHOD. FBC 1803. |
| | |
| | 5) THE ELEVATIONS FOR THE BUILDING AND SITE USE NGVD 29 |
| | VERTICAL DATUM. THE CURRENT FLOOD INSURANCE RATE MAPS |
| | USE NAVD 88 VERTICAL DATUM. THESE MAPS WERE ADOPTED BY |
| | THE CITY ON OCT 5, 2017. IN ORDER TO AVOID CONFUSION |
| | AND POSSIBLE ERRORS PLEASE SPECIFY THE ELEVATIONS USING |
| | THE CURRENT NAVD 88 DATUM. FBC 107.2.1 |
| | |
| | 6) ON SHEET A-1.00, THE FIRE SEPARATION DISTANCE ON THE |
| | NORTH SIDE OF THE BUILDING TO THE PROPERTY LINE IS ONLY |
| | 3'-10" AT THE MERCANTILE OCCUPANCY AT THE NORTHWEST |
| | CORNER AND 1'-1" AT THE NORTHEAST CORNER. NO OPENINGS |
| | ARE ALLOWED FOR LESS THAN 3' OF FIRE SEPARATION |
| | DISTANCE AND FROM 3' TO LESS THAN 5' ONLY 15 PERCENT OF |
| | WALL AREA PER STORY IS ALLOWED. SEE FBC TABLE 705.8 I |
| | UNDERSTAND THAT THERE IS A RESTRICTIVE COVENANT IN |
| | PROGRESS THAT IF APPROVED WILL CHANGE THE FIRE |
| | SEPARATION DISTANCE. WHEN THIS HAS BEEN APPROVED I WILL |
| | RE-VISIT THIS ISSUE. THE PROPOSED FIRE SEPARATION |
| | APPEARS TO BE LESS THAN 20' FOR MOST OF THE BUILDING ON |
| | THE NORTH SIDE. FBC TABLE 705.8 ALLOWS 75 PERCENT |
| | OPENINGS FOR A FSD OF 15' TO LESS THAN 20' AND |
| | UNLIMITED OPENINGS FOR A FSD OF 20' OR MORE PER STORY |
| | FOR A FULLY SPRINKLERED BUILDING. A CLEAR PLAN SHOWING |
| | THE FIRE SEPARATION DISTANCE AND CALCULATIONS WILL BE |
| | REQUIRED IF LESS THAN 20' OF FIRE SEPARATION DISTANCE. |
| | YOU MAY NEED TO REVISE THE INFORMATION IN THE FIRE |
| | SEPARATION SCHEDULES ON SHEET A-0.02. |
| | |
| | 7) ALSO ON SHEET A-1.00 THE FIRE SEPARATION DISTANCE ON |
| | THE EAST END OF THE BUILDING IS 15'-7" FOR THE GROUND |
| | AND SECOND LEVEL (BASE) WHICH ALLOWS 75 PERCENT FOR A |
| | FSD OF 15' TO LESS THAN 20'. PROVIDE THE CALCULATIONS |
| | FOR EACH STORY TO SHOW COMPLIANCE WITH FBC TABLE 705.8. |
| | NOTE: IN THE FIRE SEPARATION SCHEDULE ON SHEET A-0.02 |
| | THE INFORMATION IS REVERSED FOR THE BASE AND THE TOWER. |
| | |
| | 8) ONE OF THE REQUIRED EXITS FROM THE MERCANTILE |
| | OCCUPANCY (RETAIL SPACE #1) EXISTS INTO THE S-2 |
| | OCCUPANCY (PARKING GARAGE). THE LIFE SAFETY PLAN DOES |
| | NOT SHOW A RATED CORRIDOR SEPARATED FROM THE PARKING |
| | GARAGE THAT LEADS TO THE EXIT DISCHARGE. FBC 1016.2 |
| | |
| | 9) THE PLANS SHOW AN EXIT PASSAGEWAY CONNECTION |
| | INTERIOR EXIT STAIR 2 TO THE EXIT DISCHARGE. LABEL THIS |
| | EXIT PASSAGEWAY AND PROVIDE A NOTE STATING THAT NO |
| | OPENINGS OR PENETRATIONS ARE ALLOWED EXCEPT THOSE |
| | REQUIRED FOR EXITING OR NECESSARY TO SERVICE OR PROTECT |
| | THE EXIT COMPONENT. FBC 1024 & 1023.3.1 |
| | |
| | 10) THE SECTION OF STAIR 2 ON SHEET A-7.01 SHOWS 8" |
| | RISERS AT THE SECOND FLOOR. PLEASE CORRECT. FBC |
| | 1011.5.2 |
| | |
| | 11) ONE OF THE THE REQUIRED EXITS FROM THE POOL DECK |
| | AREA PASSES THROUGH THE ROOF TOP GARDEN AND THE |
| | COMMUNITY ROOM. EXPLAIN HOW THIS WILL MEET THE |
| | REQUIREMENTS OF FBC 1016.2. |
| | |
| | 12) THE DOUBLE DOORS AT THE COMMUNITY ROOM SWING OUT |
| | INTO THE CORRIDOR AND APPEAR TO ENCROACH INTO THE |
| | REQUIRED MEANS OF EGRESS WIDTH MORE THAN ALLOWED BY FBC |
| | 1005.7.1. |
| | |
| | 13) CLARIFY THE FIRE RATING OF THE TRASH CHUTE |
| | VESTIBULE AND ITS DOOR TO THE CORRIDOR. CLARIFY THE |
| | FIRE RATING OF THE OPENING INTO THE REQUIRED 2 HOUR |
| | FIRE RATED SHAFT FOR THE TRASH CHUTE. FBC 713.13 |
| | |
| | 14) THE LIFE SAFETY PLANS HAVE A NOTE AT THE ELEVATORS |
| | THAT REFERS TO AN AREA OF REFUGE. AREA OF REFUGE IS NO |
| | LONGER IN THE FBC. THAT SECTION IS NOTED AS RESERVED IN |
| | THE 2017 FBC. SINCE THIS IS NO LONGER A CODE |
| | REQUIREMENT AND THE PLANS DO NOT EVEN SHOW THE REQUIRED |
| | FIRE AND SMOKE PROTECTED AREA, THIS NOTE SHOULD BE |
| | REMOVED FROM THE DRAWINGS. FBC 107.2.1 AND 1009.6 |
| | |
| | 15) SHOW THAT THERE IS AN ELEVATOR THAT COMPLIES WITH |
| | FBC 3002.4 FOR THE ABILITY TO ACCOMMODATE AN AMBULANCE |
| | STRETCHER. |
| | |
| | 16) IDENTIFY THE VAN PARKING SPACES ON THE PLANS AND |
| | SHOW THAT THE MINIMUM REQUIRED 8'-2" CLEARANCE WILL BE |
| | MAINTAINED AS REQUIRED BY FBC ACCESSIBILITY 502.5 |
| | VERTICAL CLEARANCE. |
| | PARKING SPACES FOR VANS AND ACCESS AISLES AND VEHICULAR |
| | ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE |
| | OF 98 INCHES (2490 MM) MINIMUM. NOTE: FLORIDA LAW, |
| | S.553.511, F.S., REQUIRES SIGNS BE POSTED THAT WILL |
| | WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF HEIGHT |
| | LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT WHERE |
| | THE VAN CANNOT BE MANEUVERED. |
| | |
| | 17) THE DOOR FROM THE GYM TO THE YOGA ROOM DOES NOT |
| | APPEAR TO HAVE THE REQUIRED 18" CLEAR ON THE PULL SIDE |
| | FOR MANEUVERING CLEARANCE. FBC ACCESSIBILITY 404.2.4.1 |
| | |
| | 18) THE SPACE ABOVE RETAIL SPACE 1 APPEARS TO BE A |
| | STORY RATHER THAN A MEZZANINE AS SPECIFIED ON THE |
| | PLANS. CLARIFY HOW THIS AREA IS A MEZZANINE AND SHOW |
| | COMPLIANCE WITH FBC 201.1.1 VERTICAL ACCESSIBILITY. |
| | SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS |
| | FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: |
| | 1.ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL ROOMS, |
| | PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE LUBRICATION |
| | AND MAINTENANCE PITS AND PLATFORMS. |
| | 2.UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN |
| | OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS. |
| | 3.OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE |
| | PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS, |
| | INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. |
| | 4.THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER LARGE |
| | ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR |
| | TIERED SEATING IF SECTIONS 221 AND 802 ARE MET. |
| | 5.ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF |
| | CHAPTER 10 ARE MET. |
| | 6.ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9. |
| | 7.FACILITIES, SITES AND SPACES EXEMPTED BY SECTION 203. |
| | |
| | 19) IT APPEARS THAT THIS PROJECT WILL BE USING |
| | GOVERNMENT FUNDING WHICH WILL REQUIRE THAT ACCESSIBLE |
| | ENTRANCE INTO THE POOL WILL BE REQUIRED. SHOW HOW THE |
| | NEW POOL WILL COMPLY WITH FBC ACCESSIBILITY SECTION |
| | 242.2 SWIMMING POOLS. AT LEAST TWO ACCESSIBLE MEANS OF |
| | ENTRY SHALL BE PROVIDED FOR SWIMMING POOLS. ACCESSIBLE |
| | MEANS OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING |
| | WITH 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3; |
| | TRANSFER WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS |
| | COMPLYING WITH 1009.5; AND POOL STAIRS COMPLYING WITH |
| | 1009.6. AT LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED |
| | SHALL COMPLY WITH 1009.2 OR 1009.3. |
| | |
| | 20) THE TEST REPORTS FOR THE SOUND INSULATION SPECIFIED |
| | ON SHEET A-9.03 FOR FBC 603.1 FLAME SPREAD - ASTM E |
| | 84-09, FBC 1207.2 AIR-BORNE SOUND ASTM E 90-04, AND FBC |
| | 1207.3 STRUCTURE-BORNE SOUND ASTM E 492-09 WILL HAVE TO |
| | BE SUBMITTED. |
| | |
| | 21) THE SPECIFICATIONS, TEST REPORTS AND INSTALLATION |
| | REQUIREMENTS WILL BE REQUIRED FOR THE FIRE RATED GLASS |
| | ASSEMBLIES IN THE CORRIDOR WALLS OF THE COMMUNITY ROOM. |
| | FBC 716.6 |
| | |
| | 22) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| | DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| | BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED |
| | TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 23) THE DESIGN PROFESSIONAL SHOULD PROVIDE A LIST OF |
| | ITEMS ON THE PLANS THAT THEY WISH TO BE SUBMITTED AND |
| | APPROVED AFTER THE PERMIT IS ISSUED BUT PRIOR TO THE |
| | INSTALLATION OF THE PRODUCT. FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL |
| | IN RESPONSIBLE CHARGE SHALL LIST THE DEFERRED |
| | SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY |
| | THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 24) SHOP DRAWINGS AND SUBMITTALS FROM DELEGATE |
| | ENGINEERS SHALL BE REVIEWED AND APPROVED FOR DESIGN |
| | COMPLIANCE BY THE DESIGNER OF RECORD FOR THE PROJECT |
| | AND THE CONTRACTOR BEFORE SUBMITTING FOR REVIEW BY THE |
| | BUILDING DEPARTMENT. FBC107.3.4.1 |
| | |
| | 25) PLEASE CLARIFY IF THE INTENT OF THE DESIGN IS FOR |
| | ONE OR BOTH TIERS OF THE PARKING GARAGE TO BE OPEN OR |
| | ENCLOSED. THE AMOUNT OF ALLOWABLE OPENINGS IN COMMENT |
| | NUMBERS 6 AND 7 WILL HAVE AN AFFECT ON THIS |
| | REQUIREMENT. THE CALCULATIONS DO NOT APPEAR TO BE |
| | CORRECT. THE ENTIRE PERIMETER WALL AREA OF EACH TIER |
| | AND THE TOTAL ENTIRE PERIMETER WALL LENGTH OF EACH TIER |
| | ARE REQUIRED TO BE USED IN THE CALCULATIONS. THE AREA |
| | OF OPENINGS IN THE INTERIOR WALLS MUST BE AT LEAST 20 |
| | PERCENT OF THE AREA OF THE INTERIOR WALLS WITH THE |
| | OPENINGS OPENLY DISTRIBUTED, THE STRUCTURAL BEAMS AND |
| | COLUMNS ARE CONSIDERED WALL AREA. FBC 406.5 |
| | |
| | 26) SEPARATE PERMITS, APPLICATIONS AND FEES ARE |
| | REQUIRED FOR: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | PARKING LOT |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | IN ORDER TO AVOID BEING OVERCHARGED FOR PERMIT FEES |
| | PROVIDE A LIST WITH THE COSTS OF THE ITEMS THAT WILL |
| | REQUIRE SEPARATE PERMITS SO THEY CAN BE DEDUCTED FROM |
| | THE FEES FOR THIS PERMIT. FBC 109.3 |
| | |
| | 27) SUBMIT A SQUARE FOOT TABULATION OF THE AREA FOR |
| | EACH OF THE DIFFERENT OCCUPANCY TYPES IN THIS MIXED USE |
| | BUILDING. FBC 107.2.1 & 109.3 |
| | |
| | 28) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |