Plan Review Notes
Plan Review Notes For Permit 20080364
Permit Number 20080364
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-03 10:38:00PLAN
 REVIEW COMMENTS
 THRESHOLD BUILDING
 8 STORY APARTMENT BUILDING (MIXED USE R-2, M, S-2 )
 CONST. TYPE 1-B, SPRINKLERED
 170 MPH, EXPOSURE "C"
 FLOOD ZONE "X"
 951 BANYAN
 PERMIT #20080364
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS IS A THRESHOLD BUILDING / FL S. S. 553.71(7).
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) SUBMIT MANAGEMENT OF TRAFFIC (MOT) PLANS AND SPECIFY
 HOW COMPLIANCE WITH FBC CHAPTER 33 SAFEGUARDS DURING
 CONSTRUCTION FOR THE FOUNDATION PERMIT WILL BE MET.
  
 3) THE PROJECT APPEARS TO ENCOMPASS SEVERAL PARCELS OR
 LOTS. A UNITY OF TITLE WILL BE REQUIRED BEFORE THE
 PERMIT IS ISSUED. FBC 107.2.1
  
 4) SUBMIT A GEOTECHNICAL REPORT THAT SPECIFIES THE
 REQUIRED SOIL BEARING CAPACITY AND THE RECOMMENDED SOIL
 PREPARATION METHOD. FBC 1803.
  
 5) THE ELEVATIONS FOR THE BUILDING AND SITE USE NGVD 29
 VERTICAL DATUM. THE CURRENT FLOOD INSURANCE RATE MAPS
 USE NAVD 88 VERTICAL DATUM. THESE MAPS WERE ADOPTED BY
 THE CITY ON OCT 5, 2017. IN ORDER TO AVOID CONFUSION
 AND POSSIBLE ERRORS PLEASE SPECIFY THE ELEVATIONS USING
 THE CURRENT NAVD 88 DATUM. FBC 107.2.1
  
 6) ON SHEET A-1.00, THE FIRE SEPARATION DISTANCE ON THE
 NORTH SIDE OF THE BUILDING TO THE PROPERTY LINE IS ONLY
 3'-10" AT THE MERCANTILE OCCUPANCY AT THE NORTHWEST
 CORNER AND 1'-1" AT THE NORTHEAST CORNER. NO OPENINGS
 ARE ALLOWED FOR LESS THAN 3' OF FIRE SEPARATION
 DISTANCE AND FROM 3' TO LESS THAN 5' ONLY 15 PERCENT OF
 WALL AREA PER STORY IS ALLOWED. SEE FBC TABLE 705.8 I
 UNDERSTAND THAT THERE IS A RESTRICTIVE COVENANT IN
 PROGRESS THAT IF APPROVED WILL CHANGE THE FIRE
 SEPARATION DISTANCE. WHEN THIS HAS BEEN APPROVED I WILL
 RE-VISIT THIS ISSUE. THE PROPOSED FIRE SEPARATION
 APPEARS TO BE LESS THAN 20' FOR MOST OF THE BUILDING ON
 THE NORTH SIDE. FBC TABLE 705.8 ALLOWS 75 PERCENT
 OPENINGS FOR A FSD OF 15' TO LESS THAN 20' AND
 UNLIMITED OPENINGS FOR A FSD OF 20' OR MORE PER STORY
 FOR A FULLY SPRINKLERED BUILDING. A CLEAR PLAN SHOWING
 THE FIRE SEPARATION DISTANCE AND CALCULATIONS WILL BE
 REQUIRED IF LESS THAN 20' OF FIRE SEPARATION DISTANCE.
 YOU MAY NEED TO REVISE THE INFORMATION IN THE FIRE
 SEPARATION SCHEDULES ON SHEET A-0.02.
  
 7) ALSO ON SHEET A-1.00 THE FIRE SEPARATION DISTANCE ON
 THE EAST END OF THE BUILDING IS 15'-7" FOR THE GROUND
 AND SECOND LEVEL (BASE) WHICH ALLOWS 75 PERCENT FOR A
 FSD OF 15' TO LESS THAN 20'. PROVIDE THE CALCULATIONS
 FOR EACH STORY TO SHOW COMPLIANCE WITH FBC TABLE 705.8.
 NOTE: IN THE FIRE SEPARATION SCHEDULE ON SHEET A-0.02
 THE INFORMATION IS REVERSED FOR THE BASE AND THE TOWER.
  
 8) ONE OF THE REQUIRED EXITS FROM THE MERCANTILE
 OCCUPANCY (RETAIL SPACE #1) EXISTS INTO THE S-2
 OCCUPANCY (PARKING GARAGE). THE LIFE SAFETY PLAN DOES
 NOT SHOW A RATED CORRIDOR SEPARATED FROM THE PARKING
 GARAGE THAT LEADS TO THE EXIT DISCHARGE. FBC 1016.2
  
 9) THE PLANS SHOW AN EXIT PASSAGEWAY CONNECTION
 INTERIOR EXIT STAIR 2 TO THE EXIT DISCHARGE. LABEL THIS
 EXIT PASSAGEWAY AND PROVIDE A NOTE STATING THAT NO
 OPENINGS OR PENETRATIONS ARE ALLOWED EXCEPT THOSE
 REQUIRED FOR EXITING OR NECESSARY TO SERVICE OR PROTECT
 THE EXIT COMPONENT. FBC 1024 & 1023.3.1
  
 10) THE SECTION OF STAIR 2 ON SHEET A-7.01 SHOWS 8"
 RISERS AT THE SECOND FLOOR. PLEASE CORRECT. FBC
 1011.5.2
  
 11) ONE OF THE THE REQUIRED EXITS FROM THE POOL DECK
 AREA PASSES THROUGH THE ROOF TOP GARDEN AND THE
 COMMUNITY ROOM. EXPLAIN HOW THIS WILL MEET THE
 REQUIREMENTS OF FBC 1016.2.
  
 12) THE DOUBLE DOORS AT THE COMMUNITY ROOM SWING OUT
 INTO THE CORRIDOR AND APPEAR TO ENCROACH INTO THE
 REQUIRED MEANS OF EGRESS WIDTH MORE THAN ALLOWED BY FBC
 1005.7.1.
  
 13) CLARIFY THE FIRE RATING OF THE TRASH CHUTE
 VESTIBULE AND ITS DOOR TO THE CORRIDOR. CLARIFY THE
 FIRE RATING OF THE OPENING INTO THE REQUIRED 2 HOUR
 FIRE RATED SHAFT FOR THE TRASH CHUTE. FBC 713.13
  
 14) THE LIFE SAFETY PLANS HAVE A NOTE AT THE ELEVATORS
 THAT REFERS TO AN AREA OF REFUGE. AREA OF REFUGE IS NO
 LONGER IN THE FBC. THAT SECTION IS NOTED AS RESERVED IN
 THE 2017 FBC. SINCE THIS IS NO LONGER A CODE
 REQUIREMENT AND THE PLANS DO NOT EVEN SHOW THE REQUIRED
 FIRE AND SMOKE PROTECTED AREA, THIS NOTE SHOULD BE
 REMOVED FROM THE DRAWINGS. FBC 107.2.1 AND 1009.6
  
 15) SHOW THAT THERE IS AN ELEVATOR THAT COMPLIES WITH
 FBC 3002.4 FOR THE ABILITY TO ACCOMMODATE AN AMBULANCE
 STRETCHER.
  
 16) IDENTIFY THE VAN PARKING SPACES ON THE PLANS AND
 SHOW THAT THE MINIMUM REQUIRED 8'-2" CLEARANCE WILL BE
 MAINTAINED AS REQUIRED BY FBC ACCESSIBILITY 502.5
 VERTICAL CLEARANCE.
 PARKING SPACES FOR VANS AND ACCESS AISLES AND VEHICULAR
 ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE
 OF 98 INCHES (2490 MM) MINIMUM. NOTE: FLORIDA LAW,
 S.553.511, F.S., REQUIRES SIGNS BE POSTED THAT WILL
 WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF HEIGHT
 LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT WHERE
 THE VAN CANNOT BE MANEUVERED.
  
 17) THE DOOR FROM THE GYM TO THE YOGA ROOM DOES NOT
 APPEAR TO HAVE THE REQUIRED 18" CLEAR ON THE PULL SIDE
 FOR MANEUVERING CLEARANCE. FBC ACCESSIBILITY 404.2.4.1
  
 18) THE SPACE ABOVE RETAIL SPACE 1 APPEARS TO BE A
 STORY RATHER THAN A MEZZANINE AS SPECIFIED ON THE
 PLANS. CLARIFY HOW THIS AREA IS A MEZZANINE AND SHOW
 COMPLIANCE WITH FBC 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR:
 1.ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL ROOMS,
 PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE LUBRICATION
 AND MAINTENANCE PITS AND PLATFORMS.
 2.UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES
 AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN
 OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS.
 3.OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE
 PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS,
 INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS.
 4.THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER LARGE
 ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR
 TIERED SEATING IF SECTIONS 221 AND 802 ARE MET.
 5.ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF
 CHAPTER 10 ARE MET.
 6.ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9.
 7.FACILITIES, SITES AND SPACES EXEMPTED BY SECTION 203.
  
 19) IT APPEARS THAT THIS PROJECT WILL BE USING
 GOVERNMENT FUNDING WHICH WILL REQUIRE THAT ACCESSIBLE
 ENTRANCE INTO THE POOL WILL BE REQUIRED. SHOW HOW THE
 NEW POOL WILL COMPLY WITH FBC ACCESSIBILITY SECTION
 242.2 SWIMMING POOLS. AT LEAST TWO ACCESSIBLE MEANS OF
 ENTRY SHALL BE PROVIDED FOR SWIMMING POOLS. ACCESSIBLE
 MEANS OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING
 WITH 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3;
 TRANSFER WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS
 COMPLYING WITH 1009.5; AND POOL STAIRS COMPLYING WITH
 1009.6. AT LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED
 SHALL COMPLY WITH 1009.2 OR 1009.3.
  
 20) THE TEST REPORTS FOR THE SOUND INSULATION SPECIFIED
 ON SHEET A-9.03 FOR FBC 603.1 FLAME SPREAD - ASTM E
 84-09, FBC 1207.2 AIR-BORNE SOUND ASTM E 90-04, AND FBC
 1207.3 STRUCTURE-BORNE SOUND ASTM E 492-09 WILL HAVE TO
 BE SUBMITTED.
  
 21) THE SPECIFICATIONS, TEST REPORTS AND INSTALLATION
 REQUIREMENTS WILL BE REQUIRED FOR THE FIRE RATED GLASS
 ASSEMBLIES IN THE CORRIDOR WALLS OF THE COMMUNITY ROOM.
 FBC 716.6
  
 22) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 23) THE DESIGN PROFESSIONAL SHOULD PROVIDE A LIST OF
 ITEMS ON THE PLANS THAT THEY WISH TO BE SUBMITTED AND
 APPROVED AFTER THE PERMIT IS ISSUED BUT PRIOR TO THE
 INSTALLATION OF THE PRODUCT. FBC 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL
 IN RESPONSIBLE CHARGE SHALL LIST THE DEFERRED
 SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY
 THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 24) SHOP DRAWINGS AND SUBMITTALS FROM DELEGATE
 ENGINEERS SHALL BE REVIEWED AND APPROVED FOR DESIGN
 COMPLIANCE BY THE DESIGNER OF RECORD FOR THE PROJECT
 AND THE CONTRACTOR BEFORE SUBMITTING FOR REVIEW BY THE
 BUILDING DEPARTMENT. FBC107.3.4.1
  
 25) PLEASE CLARIFY IF THE INTENT OF THE DESIGN IS FOR
 ONE OR BOTH TIERS OF THE PARKING GARAGE TO BE OPEN OR
 ENCLOSED. THE AMOUNT OF ALLOWABLE OPENINGS IN COMMENT
 NUMBERS 6 AND 7 WILL HAVE AN AFFECT ON THIS
 REQUIREMENT. THE CALCULATIONS DO NOT APPEAR TO BE
 CORRECT. THE ENTIRE PERIMETER WALL AREA OF EACH TIER
 AND THE TOTAL ENTIRE PERIMETER WALL LENGTH OF EACH TIER
 ARE REQUIRED TO BE USED IN THE CALCULATIONS. THE AREA
 OF OPENINGS IN THE INTERIOR WALLS MUST BE AT LEAST 20
 PERCENT OF THE AREA OF THE INTERIOR WALLS WITH THE
 OPENINGS OPENLY DISTRIBUTED, THE STRUCTURAL BEAMS AND
 COLUMNS ARE CONSIDERED WALL AREA. FBC 406.5
  
 26) SEPARATE PERMITS, APPLICATIONS AND FEES ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 ALL OTHER ITEMS OTHER THAN BMEP
 IN ORDER TO AVOID BEING OVERCHARGED FOR PERMIT FEES
 PROVIDE A LIST WITH THE COSTS OF THE ITEMS THAT WILL
 REQUIRE SEPARATE PERMITS SO THEY CAN BE DEDUCTED FROM
 THE FEES FOR THIS PERMIT. FBC 109.3
  
 27) SUBMIT A SQUARE FOOT TABULATION OF THE AREA FOR
 EACH OF THE DIFFERENT OCCUPANCY TYPES IN THIS MIXED USE
 BUILDING. FBC 107.2.1 & 109.3
  
 28) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  
  
  