Plan Review Notes
Plan Review Notes For Permit 20080353
Permit Number 20080353
Review Stop M
Sequence Number 2
Notes
Date Text
2020-10-14 07:49:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080353
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OCCUPANCY AND USE OF SPACE FOR
 THIS BUILDING. FBC M TABLE 403.3.1.1
  
 2) PLEASE PROVIDE OUTSIDE AIR CALCULATIONS FOR USE OF
 THIS BUILDING BROKEN DOWN TO EACH AHU. FBC M TABLE
 403.3.1.1
  
 3) REST ROOM B3 IS MISSING AN EXHAUST FAN. PLEASE SHOW
 HOW THIS ROOM WILL BE VENTILATED. FBC M TABLE 403.3.2.3
  
 4) SHEET M0: EF-1 INDICATES AREA SERVED AS MASTER BATH,
 THIS IS A COMMERCIAL BUILDING. PLEASE INDICATE THE
 CORRECT NAME OF THE LOCATION OF THE EF-1. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  