| 2020-10-14 07:49:50 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20080353 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE OCCUPANCY AND USE OF SPACE FOR |
| | THIS BUILDING. FBC M TABLE 403.3.1.1 |
| | |
| | 2) PLEASE PROVIDE OUTSIDE AIR CALCULATIONS FOR USE OF |
| | THIS BUILDING BROKEN DOWN TO EACH AHU. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 3) REST ROOM B3 IS MISSING AN EXHAUST FAN. PLEASE SHOW |
| | HOW THIS ROOM WILL BE VENTILATED. FBC M TABLE 403.3.2.3 |
| | |
| | 4) SHEET M0: EF-1 INDICATES AREA SERVED AS MASTER BATH, |
| | THIS IS A COMMERCIAL BUILDING. PLEASE INDICATE THE |
| | CORRECT NAME OF THE LOCATION OF THE EF-1. FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |