| Plan Review Notes For Permit 20080353 |
| Permit Number |
20080353 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-15 12:36:31 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | FBC B 107, PROVIDE THE FOLLOWING INFORMATION: | | | | | | 1) FBC M 304.1, PROVIDE MOUNTING DETAILS FOR AIR | | | HANDLER UNITS 3,4 & 5. | | | 2) FBC M 304.1 & 301.15, PROVIDE MOUNTING DETAILS FOR | | | THE OUTSIDE AIR ROOF TOP INTAKES. | | | 3) FBC M 603.18, FBC M 603.3, PROVIDE LOCATIONS OF ALL | | | ACCESS DOORS FOR SMOKE DETECTORS, DAMPERS AND | | | REGISTERS. |
|