 MECHANICAL REVIEW DENIED:
  
 FBC B 107, PROVIDE THE FOLLOWING INFORMATION:
  
 1) FBC M 304.1, PROVIDE MOUNTING DETAILS FOR AIR
 HANDLER UNITS 3,4 & 5.
 2) FBC M 304.1 & 301.15, PROVIDE MOUNTING DETAILS FOR
 THE OUTSIDE AIR ROOF TOP INTAKES.
 3) FBC M 603.18, FBC M 603.3, PROVIDE LOCATIONS OF ALL
 ACCESS DOORS FOR SMOKE DETECTORS, DAMPERS AND
 REGISTERS.