2020-08-07 10:42:40THE PROPOSED DEMOLITION IS TO COMPLY WITH THE
 SAFEGAURDS OUTLINNED IN NFPA 241, TO INCLUDE, BUT IS
 NOT LIMITED TO:
  
 5.1 HOT WORK.
 5.1.1* RESPONSIBILITY FOR HOT WORK OPERATIONS AND FIRE
 PREVENTION
 PRECAUTIONS, INCLUDING PERMITS AND FIRE WATCHES, SHALL
 BE
 IN ACCORDANCE WITH NFPA 51B, STANDARD FOR FIRE
 PREVENTION DURING
 WELDING, CUTTING, AND OTHER HOT WORK, EXCEPT AS
 MODIFIED IN
 CHAPTER 9.
 5.1.2 GAS-OPERATED CUTTING AND WELDING EQUIPMENT USING
 MULTIPLE OXYGEN AND FUEL GAS CYLINDERS SHALL BE IN
 ACCORDANCE
 WITH NFPA 51, STANDARD FOR THE DESIGN AND INSTALLATION
 OF OXYGEN?
 FUEL GAS SYSTEMS FOR WELDING, CUTTING, AND ALLIED
 PROCESSES.
  
 5.1.3.2 A FIRE WATCH SHALL BE POSTED FOR THE DURATION
 OF THE
 WORK AND FOR 2 HOURS THEREAFTER FOR TORCH-APPLIED
 ROOFING OPERATIONS
 (SEE 9.3.9).
  
 6.1 ELECTRICAL.
 6.1.1 ALL CONSTRUCTION-OPERATION ELECTRICAL WIRING AND
 EQUIPMENT
 FOR LIGHT, HEAT, OR POWER PURPOSES SHALL BE IN
 ACCORDANCE
 WITH THE APPLICABLE PROVISIONS OF NFPA 70, NATIONAL
 ELECTRICAL CODE.
  
 6.1.1.3 DAMAGED EQUIPMENT AND CORDS SHALL BE REMOVED
 FROM SERVICE UNTIL RENDERED SAFE.
  
 7.2 OWNER?S RESPONSIBILITY FOR FIRE PROTECTION.
 7.2.1* THE OWNER SHALL DESIGNATE A PERSON WHO SHALL BE
 RESPONSIBLE
 FOR THE FIRE PREVENTION PROGRAM AND WHO SHALL ENSURE
 THAT IT IS CARRIED OUT TO COMPLETION.
 7.2.1.1 THE FIRE PREVENTION PROGRAM MANAGER SHALL HAVE
 THE
 AUTHORITY TO ENFORCE THE PROVISIONS OF THIS AND OTHER
 APPLICABLE
 FIRE PROTECTION STANDARDS.
  
 7.5.8 HYDRANTS.
 7.5.8.1 FREE ACCESS FROM THE STREET TO FIRE HYDRANTS
 AND TO
 OUTSIDE CONNECTIONS FOR STANDPIPES, SPRINKLERS, OR
 OTHER FIRE
 EXTINGUISHING EQUIPMENT, WHETHER PERMANENT OR
 TEMPORARY,
 SHALL BE PROVIDED AND MAINTAINED AT ALL TIMES.
 7.5.8.2 PROTECTIVE PEDESTRIAN WALKWAYS SHALL NOT BE
 CONSTRUCTED
 SO THAT THEY IMPEDE ACCESS TO HYDRANTS.
 7.5.8.3 NO MATERIAL OR CONSTRUCTION SHALL INTERFERE
 WITH ACCESS TO
 HYDRANTS, SIAMESE CONNECTIONS, OR FIRE EXTINGUISHING
 EQUIPMENT.
  
 7.5.5.2 ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS
 SHALL BE
 PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE
 PROJECT
 AND MAINTAINED UNTIL COMPLETION.
  
 CHAPTER 10 SAFEGUARDING DEMOLITION OPERATIONS
 10.1 GENERAL. IN ADDITION TO THE SPECIFIC REQUIREMENTS
 OF THIS
 CHAPTER, THE PROVISIONS OF CHAPTER 1 AND CHAPTERS 3
 THROUGH 7
 SHALL BE FOLLOWED, AS APPLICABLE, FOR ALL DEMOLITION
 OPERATIONS
  
 10.6 UTILITIES.
 10.6.1 ELECTRICAL SERVICE. ELECTRICAL SERVICE SHALL BE
 REDUCED TO
 A MINIMUM, AND THE IDENTITY OF ENERGIZED CIRCUITS SHALL
 BE
 ENSURED TO AVOID ANY UNCERTAINTY.
 10.6.2 GAS.
 10.6.2.1 PRIOR TO DEMOLITION, GAS SUPPLIES SHALL BE
 TURNED OFF
 AND CAPPED AT A POINT OUTSIDE THE BUILDING.
 10.6.2.2 GAS LINES WITHIN THE BUILDING SHALL BE PURGED
 AFTER
 CAPPING UNLESS OTHERWISE PERMITTED BY THE AUTHORITY
 HAVING
 JURISDICTION.
  
 PLEASE ENSURE FIRE AND LIFE SAFETY WITH COMPLIANCE OF
 THE CODE
  
  