| 2020-08-20 07:54:04 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20080325 |
| | 8/20/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1: THE ISOMETRIC DRAWING APPEARS TO SHOW THE |
| | 2" TUB DRAIN CONNECTING VERTICALLY INTO THE WET VENT. |
| | THE DRAIN SHALL CONNECT HORIZONTALLY OTHERWISE IT MUST |
| | BE INDIVIDUALLY VENTED- SECTION P3108.1 FBC RES. |
| | |
| | 2) A2 & P-1: PLEASE PROVIDE A SCOPE OF WORK FOR THE |
| | WATER HEATER. IT APPEARS TO BE A REPLACEMENT OF THE |
| | EXISTING. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON THE |
| | PLAN THAT INCLUDES THE EFFICIENCY RATING OF THE |
| | APPLIANCE, AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | TABLE C404.2 FBC EC AND SECTION P2801.3 FBC RES. |
| | |
| | 3) A2 & P1: INDICATE HOW THE WH IN THE GARAGE WILL BE |
| | PROTECTED AGAINST VEHICLE IMPACT- SECTIONS P2801.4, |
| | P2801.5, & M1307.3.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |