| Plan Review Notes For Permit 20080325 |
| Permit Number |
20080325 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-16 13:50:17 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW ALL STAIR RISER HEIGHTS TO HAVE A MAX. | | | 3/8" DIFFERENCE FBC R311.7.5 | | | 2) PLEASE SHOW TREAD DEPTHS TO COMPLY WITH FBC R311.7.5 | | | 3) PLEASE SHOW NEW ADDITION ATTIC AREA VENTILATION TO | | | COMPLY WITH FBC R807 | | | 4) PLEASE SHOW THE LOCATION AND SIZE OF THE ATTIC | | | ACCESS TO THE NEW ADDITION - FBC R807 | | | 5) PRODUCT APPROVAL (FL243 R21) HAS EXPIRED - PLEASE | | | PROVIDE AN UPDATED PRODUCT APPROVAL FOR THE FIXED | | | GLASS. | | | |
|