| 2020-08-12 18:18:35 | 08/12/20 1ST PLUMBING/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING PERMIT FOR ANY EXISTING SYSTEM (GAS AND |
| | PLUMBING). A FULL EVALUATION OF ALL EQUIPMENT WILL BE |
| | DONE, IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE |
| | COMPLIANCE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SUBMIT COPIES OF MANUFACTURES SPECIFICATION FOR ALL |
| | EQUIPMENT EACH PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | (TANKLESS, BBQ AND POOL HEATER). |
| | |
| | 3. THE TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE |
| | THE COST OF ALL EQUIPMENT INCLUDING POOL HEATER, |
| | TANKLESS AND BBQ. PROVIDE BONA FIDE SIGNED CONTRACT PER |
| | THE WPB AMENDMENTS TO THE FBC 109.3. |
| | |
| | 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 5. GAS UNITS REQUIRE CONDENSATE AND THEY NEED TO BE 1' |
| | AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5. PLEASE |
| | NOT ON ISOMETRIC AND SHOW REGULATOR AND DRIP LEG. |
| | |
| | 6. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND |
| | THE SERVICE METER DISCHARGES IS A 2 PSI OR 12" WATER |
| | COLUMN IT WILL REQUIRE A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 7. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| | OF IGNITION OR REVISE CURRENT ELECTRICAL PERMIT TO |
| | REFLECT SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |