| 2020-08-24 12:13:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET A 1.01 - THE PROPOSED PROJECT AFFECTS THE MAIN | | | EGRESSES FOR THE BUILDING. | | | | | | THERE IS NO LIFE SAFETY PLAN THAT PROVIDES FOR | | | MAINTAINING SAFE EGRESS DURING THE DEMO AND OR | | | THROUGHOUT THE CONSTRUCTION PERIOD. | | | | | | PLEASE PROVIDE A LIFE SAFETY SHEET WITH THE DETAILS. | | | | | | | | | 2) SHEET A 1.01 - AS PART OF THE BUILDING LIFE SAFETY | | | SYSTEM, ARE THE ELEVATORS/CORRIDOR PRESSURIZED? | | | | | | IF SO, HOW WILL THE SYSTEM BE MAINTAINED? | | | | | | PLEASE PROVIDE A REIEW OF HOW THE PROPOSED AFFECTS ANY | | | LIFE SAFETY FEATURES. | | | | | | | | | 3) SHEET A 1.01 - THERE ARE NO INDICATIONS OF EXISTING | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS AND EQUIPMENT. | | | | | | THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE | | | MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | | | | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES | | | SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE | | | ON THE LIFE SAFETY PLAN. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|