| 2020-12-11 08:13:57 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | 2ND REVIEW |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE USE OF THE ROOM ON THE FLOOR PLAN. |
| | 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE ROOFING. (CIRCLE THE ROOFING |
| | TILE ATTACHMENT ON THE PRODUCT APPROVAL TO BE USED - IF |
| | USING ADHESIVE PLEASE PROVIDE THE MIAMI DADE OR FLORIDA |
| | STATE PRODUCT APPROVAL FOR THE ADHESIVE). |
| | 3) PLEASE PROVIDE A COPY OF THE PRODUCT APPROVAL LISTED |
| | ON THE DRAWINGS FOR THE WINDOWS. |
| | 4) PLEASE PROVIDE A ROOF FRAMING PLAN - SHOWING THE |
| | STRAPPING DETAILS AS STATED ON DRAWING (A1). |
| | 5) PLEASE SHOW THE "R" VALUE FOR THE CEILING |
| | INSULATION. |
| | 6) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE TO |
| | COMPLY WITH FBC R807.1 |
| | 7) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT - OR |
| | - PROVIDE A STATEMENT ON THE DRAWINGS FROM THE |
| | ARCHITECT STATING THE EXISTING SOIL BEARING CAPACITY |
| | MEETS THE DESIGN CAPACITY OF 2500PSF. |
| | 8) PLEASE SHOW THE LOCATION OF THE ADDITION ON THE |
| | SURVEY - OR - SITE PLAN. |
| | 9) PLEASE SHOW THE CEILING HEIGHT. |
| | 10) THE ADDED TRUSS LAYOUT AND TRUSS ENGINEERING NEEDS |
| | TO BE SIGNED AND SEALED BY THE TRUSS ENGINEER AND |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.3.4.1 |