Plan Review Notes
Plan Review Notes For Permit 20080259
Permit Number 20080259
Review Stop E
Sequence Number 3
Notes
Date Text
2021-01-11 11:52:39CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 NO ELECTRICAL CORRECTIONS HAVE BEEN SUBMITTED TO
 ADDRESS ELECTRICAL REVIEW COMMENTS FROM 11/23/2020. THE
 OUTSTANDING ITEMS ARE SHOWN BELOW:
  
 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 NOT CORRECTED. NEED TO PROVIDE LOAD CALCULATIONS FOR
 THE ENTIRE SERVICE IN ADDITION TO THE LOAD CALCULATIONS
 FOR EACH INDIVIDUAL PANEL.
  
 3.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 PANEL SCHEDULES SHOWN ARE LABELED LP1 AND LP2 WHILE
 RISER DIAGRAM AND POWER LAYOUT SHOW THEM AS PANEL A AND
 PANEL B. PLEASE CORRECT TO INDICATE PROPER NAMES OF
 PANELS. MAIN CIRCUIT BREAKERS ARE INDICATED AS 100 AMPS
 ON RISER DIAGRAM BUT AS 125 AMPS ON PANEL SCHEDULES.
 PLEASE CORRECT. ADJUST FEEDER SIZES IF NEEDED
  
 4.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 NOT CORRECTED.
  
 5.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
 NOT CORRECTED. PLEASE SHOW CONDUCTORS SIZES FOR MAIN
 SERVICE CONDUCTORS, FEEDERS TO PANELS A AND B,
 EQUIPMENT GROUNDING CONDUCTOR SIZES, PLEASE SPECIFY
 GROUNDING ELECTRODE CONDUCTOR SIZE, GROUNDING ELECTRODE
 SYSTEM.
  
 6.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 PARTIALLY CORRECTED. SMOKE DETECTOR ALSO REQUIRED IN
 LIVING/SLEEPING AREA OF STUDIO (APARTMENT B).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  