| Date |
Text |
| 2021-01-11 11:52:39 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. |
| | |
| | NO ELECTRICAL CORRECTIONS HAVE BEEN SUBMITTED TO |
| | ADDRESS ELECTRICAL REVIEW COMMENTS FROM 11/23/2020. THE |
| | OUTSTANDING ITEMS ARE SHOWN BELOW: |
| | |
| | 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | |
| | NOT CORRECTED. NEED TO PROVIDE LOAD CALCULATIONS FOR |
| | THE ENTIRE SERVICE IN ADDITION TO THE LOAD CALCULATIONS |
| | FOR EACH INDIVIDUAL PANEL. |
| | |
| | 3.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | PANEL SCHEDULES SHOWN ARE LABELED LP1 AND LP2 WHILE |
| | RISER DIAGRAM AND POWER LAYOUT SHOW THEM AS PANEL A AND |
| | PANEL B. PLEASE CORRECT TO INDICATE PROPER NAMES OF |
| | PANELS. MAIN CIRCUIT BREAKERS ARE INDICATED AS 100 AMPS |
| | ON RISER DIAGRAM BUT AS 125 AMPS ON PANEL SCHEDULES. |
| | PLEASE CORRECT. ADJUST FEEDER SIZES IF NEEDED |
| | |
| | 4.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A |
| | DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL |
| | CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | NOT CORRECTED. |
| | |
| | 5.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE |
| | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC |
| | 107.2.1 |
| | |
| | NOT CORRECTED. PLEASE SHOW CONDUCTORS SIZES FOR MAIN |
| | SERVICE CONDUCTORS, FEEDERS TO PANELS A AND B, |
| | EQUIPMENT GROUNDING CONDUCTOR SIZES, PLEASE SPECIFY |
| | GROUNDING ELECTRODE CONDUCTOR SIZE, GROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | 6.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| | 107.2.1 |
| | |
| | PARTIALLY CORRECTED. SMOKE DETECTOR ALSO REQUIRED IN |
| | LIVING/SLEEPING AREA OF STUDIO (APARTMENT B). |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | SINCERELY, |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |