| 2020-08-18 13:50:12 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC EB 505.1. REVISE CLASSIFICATION OF WORK FROM |
| | LEVEL 2 ALTERATION TO LEVEL 3 ALTERATION. |
| | 2. FBC B 310.5. REVISE OCCUPANCY GROUP TO R-3. |
| | 3. FBC B 107.2.1. REVISE WORK COMPLIANCE TO INCLUDE |
| | FBC-EXISTING BUILDING 6TH EDITION 2017. |
| | 4. FBC B 107.2.1. PLEASE CLARITY; MEAN ROOF HEIGHT |
| | SHEET CVR LISTED AS 8?-0?; PROPOSED FLOOR PLAN SHEET A1 |
| | LISTS CEILINGS HEIGHTS AS 8?-1?. |
| | 5. FBC B 107.2.1. PLEASE CLARITY; DEMOLITION PLAN SHOWS |
| | EXISTING WINDOW IN UNIT A BATH AND NO WINDOW IN UNIT B |
| | BATH. PROPOSED FLOOR PLAN DOES NOT REFLECT THE SAME. |
| | 6. FBC B 107.3.5. PROVIDE AN EXISTING AND PROPOSED NEW |
| | EXTERIOR ELEVATION DETAIL DRAWING OF THE PROPOSED |
| | EXTERIOR WORK AREA. |
| | 7. FBC-EB 903.2.1. SUBMITTED ONE HOUR FIRE RATED WALL |
| | DETAIL DRAWING DOES NOT SHOW COMPLIANCE WITH 903.2.1 OF |
| | THE 2017 FBC-EXISTING BUILDING OR THE EXCEPTION OR |
| | SECTION 708 OF THE 2017 FBC-BUILDING. REVISE TO SHOW |
| | COMPLIANCE. |
| | 8. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING MATING |
| | DETAIL OF THE PROPOSED NEW (2) 2? X 10? W ?? SPACERS |
| | WOOD BEAM AND SHOW HOW PROPOSED NEW BEAM IS CONNECTED |
| | TO EXISTING TRUSSES. |
| | 9. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING THE |
| | CONSTRUCTION METHOD OF THE PROPOSED NEW 36? SQ. PADS. |
| | 10. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING |
| | BUILDING ENVELOPE IN COMPLIANCE WITH R503.1 [RE] |
| | EXISTING BUILDING OF THE 2017 FBC-ENERGY CONSERVATION. |
| | 11. FBC B 107.2.1. REVISE WINDOW OPENING IN WOOD WALL |
| | DETAIL AND ALSO SHOW COMPLIANCE WITH R503.1 [RE] |
| | EXISTING BUILDING OF THE 2017 FBC-ENERGY CONSERVATION |
| | AND SECTION R703 OF THE 2017 FBC-RESIDENTIAL. |
| | 12. FBC B 107.2.1. PROVIDE A NAILING SCHEDULE FOR THE |
| | PROPOSED NEW ?? PLYWOOD SHEATHING SUB-FLOOR. |
| | 13. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT |
| | APPROVAL FL14911 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT) EVALUATION REPORT. |
| | PROVIDE TWO COMPLETE SETS FOR THE PROPOSED SINGLE HUNG |
| | WINDOWS USED. |
| | |