Notes
Date Text
2020-08-18 13:50:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC EB 505.1. REVISE CLASSIFICATION OF WORK FROM
 LEVEL 2 ALTERATION TO LEVEL 3 ALTERATION.
 2. FBC B 310.5. REVISE OCCUPANCY GROUP TO R-3.
 3. FBC B 107.2.1. REVISE WORK COMPLIANCE TO INCLUDE
 FBC-EXISTING BUILDING 6TH EDITION 2017.
 4. FBC B 107.2.1. PLEASE CLARITY; MEAN ROOF HEIGHT
 SHEET CVR LISTED AS 8?-0?; PROPOSED FLOOR PLAN SHEET A1
 LISTS CEILINGS HEIGHTS AS 8?-1?.
 5. FBC B 107.2.1. PLEASE CLARITY; DEMOLITION PLAN SHOWS
 EXISTING WINDOW IN UNIT A BATH AND NO WINDOW IN UNIT B
 BATH. PROPOSED FLOOR PLAN DOES NOT REFLECT THE SAME.
 6. FBC B 107.3.5. PROVIDE AN EXISTING AND PROPOSED NEW
 EXTERIOR ELEVATION DETAIL DRAWING OF THE PROPOSED
 EXTERIOR WORK AREA.
 7. FBC-EB 903.2.1. SUBMITTED ONE HOUR FIRE RATED WALL
 DETAIL DRAWING DOES NOT SHOW COMPLIANCE WITH 903.2.1 OF
 THE 2017 FBC-EXISTING BUILDING OR THE EXCEPTION OR
 SECTION 708 OF THE 2017 FBC-BUILDING. REVISE TO SHOW
 COMPLIANCE.
 8. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING MATING
 DETAIL OF THE PROPOSED NEW (2) 2? X 10? W ?? SPACERS
 WOOD BEAM AND SHOW HOW PROPOSED NEW BEAM IS CONNECTED
 TO EXISTING TRUSSES.
 9. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING THE
 CONSTRUCTION METHOD OF THE PROPOSED NEW 36? SQ. PADS.
 10. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING
 BUILDING ENVELOPE IN COMPLIANCE WITH R503.1 [RE]
 EXISTING BUILDING OF THE 2017 FBC-ENERGY CONSERVATION.
 11. FBC B 107.2.1. REVISE WINDOW OPENING IN WOOD WALL
 DETAIL AND ALSO SHOW COMPLIANCE WITH R503.1 [RE]
 EXISTING BUILDING OF THE 2017 FBC-ENERGY CONSERVATION
 AND SECTION R703 OF THE 2017 FBC-RESIDENTIAL.
 12. FBC B 107.2.1. PROVIDE A NAILING SCHEDULE FOR THE
 PROPOSED NEW ?? PLYWOOD SHEATHING SUB-FLOOR.
 13. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT
 APPROVAL FL14911 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT) EVALUATION REPORT.
 PROVIDE TWO COMPLETE SETS FOR THE PROPOSED SINGLE HUNG
 WINDOWS USED.
  