Plan Review Notes
Plan Review Notes For Permit 20080254
Permit Number 20080254
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-17 12:13:53SHED
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 2ND REVIEW
 1) DRAWINGS ADDED TO PROJECTDOX DO NOT SHOW ALL
 CONSTRUCTION DETAILS FBC 107.2 (NEED TO BE ABLE TO
 BUILD THE SHED FROM THE DRAWINGS)
 2) PLEASE PROVIDE THE WRITTEN STRUCTURAL CALCULATIONS
 FROM THE DESIGNER.
 3) DESIGNER NEEDS TO PRINT NAME ON THE DRAWINGS.
 PREVIOUS COMMENTS BELOW ARE NOT SATISFIED.
 1) THE SHED NEEDS TO MEET THE REQUIRED WIND LOADS PER
 FBC R301.2.1 - RISK CATEGORY WIND SPEED 150MPH,
 EXPOSURE "C" AND CANNOT BE CODE PRESCRIPTIVE PER FBC
 R301.2.1.1 - PLEASE PROVIDE THE STRUCTURAL CALCULATIONS
 FOR THE WIND LOADS SHOWING THAT THE CONSTRUCTION
 DRAWINGS MEET THE REQUIRED WIND LOADS OR PROVIDE SIGNED
 AND SEALED CONSTRUCTION DETAILS FROM AN ARCHITECT OR
 ENGINEER.
 2) THE DRAWINGS NEED TO SHOW THE COMPLETE CONSTRUCTION
 DETAILS (ALL ATTACHMENT, SIDING ETC.) FBC WPB
 AMENDMENTS 107.2 - FBC R301.1 (AND IF THE EXISTING SHED
 WAS BUILT WITHOUT A PERMIT IT WILL ALSO NEED TO COMPLY)
 - R301.1APPLICATION.
 BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD
 LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS,
 WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS
 CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION.
  