| 2020-08-25 10:37:27 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT APPROVAL |
| | FL1850 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL |
| | INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS |
| | WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER, |
| | STATUS, GENERAL INFORMATION ABOUT THE PRODUCT) |
| | EVALUATION REPORT. PROVIDE TWO COMPLETE SETS FOR THE |
| | PROPOSED ACCORDION SHUTTERS USED. SECOND REQUEST. |
| | 2. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| | HEADING ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT |
| | APPROVAL?; PROVIDE INFORMATION FROM SHEETS 6 & 7 OF |
| | FL1850 USE ALPHABETICAL LETTER THAT CORRESPONDS WITH |
| | THE CONNECTION TYPE FOR THE TOP AND BOTTOM CONNECTIONS. |
| | COLUMN HEADING ?ANCHOR SPACING? PROVIDE INFORMATION |
| | FROM SHEETS 12-16 FL1850. EXAMPLE SUBSTRATE CONCRETE |
| | BLOCK, MAXIMUM SPAN 7?-0? A.S.D DESIGN NEGATIVE |
| | PRESSURE RATING (PSF) 40 WALL HEADER C WALL SILL F |
| | USING TAPPER PLUS; ANCHOR SPACING IS 8? MAXIMUM. COLUMN |
| | HEADING SUBSTRATE: CONC. BLOCK, WOOD FRAME, POURED |
| | CONC. PROVIDE INFORMATION AS TO THE TYPE OF |
| | CONSTRUCTION OR ATTACHMENT SURFACE. |
| | |