| Date |
Text |
| 2020-10-26 19:34:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20080231 |
| | ADD: 651 OKEECHOBEE BLVD. # 712 |
| | CONT: FLORIDIAN PROPERTIES CORP. |
| | TEL: 561-371-1000 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. OCT. 26TH/2020 |
| | ACTION: DENIED |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 2ND REQUEST!! CERTIFICATION BY CONTRACTOR. 107.3.4.3 |
| | CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION |
| | TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/ |
| | PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES |
| | THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN |
| | THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS |
| | THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | THE REQUIRED DRAWINGS THAT ARE REQUIRED CAN BE DRAWN BY |
| | THE QUALIFIER OF THE COMPANY, FOR EACH TRADE. |
| | |
| | 3) 2ND REQUEST. THE PERMIT APPLICATION INDICATES UNDER |
| | THE SCOPE OF WORK TO REMOVE BATHROOM TUB AND SURROUND |
| | AND REPLACE NEW SHOWER. THE VALUE OF WORK DECLARED WAS |
| | $2,300.00 DOLLARS. 109.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. THE CITY?S CALCULATED DOLLAR AMOUNT IS |
| | BETWEEN $3,500.00- $4,200.00 DOLLARS DEPENDING ON THE |
| | WALL FINISHES, FLOOR FINISHES, PLUMBING DRAINAGE, TYPE |
| | OF VALVES, MULTIPLE SHOWER HEAD, WALL SPRAYS AND |
| | FINISHES ON THE PLUMBING HARDWARE. |
| | |
| | 4) 2ND REQUEST. PLEASE NOTE THIS BUILDING WAS BUILT |
| | UNDER THE FAIR HOUSING ACT. PLEASE PROVIDE THE FLOOR |
| | PLAN OF THE UNIT SHOWING WHICH BATHROOMS ARE A TYPE AND |
| | B TYPE. |
| | |
| | FAIR HOUSING GUIDELINES. FAIR HOUSING ACT DESIGN AND |
| | CONSTRUCTION REQUIREMENTS. FOR PURPOSES OF THIS |
| | SECTION, A COVERED MULTIFAMILY DWELLING SHALL BE DEEMED |
| | TO BE DESIGNED AND CONSTRUCTED FOR FIRST OCCUPANCY ON |
| | OR BEFORE MARCH 13, 1991, IF THEY ARE OCCUPIED BY THAT |
| | DATE OR IF THE LAST BUILDING PERMIT OR RENEWAL THEREOF |
| | FOR THE COVERED MULTIFAMILY DWELLINGS IS ISSUED BY A |
| | STATE, COUNTY OR LOCAL GOVERNMENT ON OR BEFORE JANUARY |
| | 13, 1990. |
| | FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER: |
| | PROJECT ADDRESS: ______________________________________ |
| | _____________________ |
| | PERMIT NUMBER: ________________________ |
| | THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| | PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS |
| | OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER |
| | AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF |
| | SALE IF SO REQUESTED BY THE BUYER. |
| | |
| | SIGNATURE OF DESIGNER: ______________________________ |
| | PRINTED NAME OF DESIGNER: ___________________________ |
| | |
| | SIGNATURE OF OWNER: ________________________________ |
| | PRINTED NAME OF OWNER: _____________________________ |
| | NOTARY FOR OWNER?S SIGNATURE: |
| | STATE OF FLORIDA, COUNTY OF PALM BEACH |
| | THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| | THIS _____ DAY OF ________, 20__ BY |
| | ___________________________ WHO IS PERSONALLY KNOWN TO |
| | ME OR WHO HAS PRODUCED: ___________________________ AS |
| | IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| | NOTARY SIGNATURE ___________________________________ |
| | NOTARY PRINTED NAME ________________________________ |
| | |
| | 5) 2ND REQUEST. PROVIDE ON THE SUBMITTED PLAN WHAT TYPE |
| | OF BACKER BOARD IS GOING TO BE INSTALLED IN THE SHOWER. |
| | 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A |
| | BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURER?S RECOMMENDATIONS. |
| | |
| | 6) 2ND REQUEST. PLEASE PROVIDE WHAT TYPE OF FINISH |
| | PRODUCT IS TO BE INSTALLED IN THE SHOWER FLOOR AND |
| | WALLS, INCLUDE THE MINIMUM HEIGHT REQUIRED FOR THE |
| | FINISHED NON-ABSORBENT SURFACE. 2017 FBC-B SHOWERS & |
| | TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS WITH |
| | INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A |
| | NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72 |
| | INCHES ABOVE THE DRAIN INLET. |
| | |
| | 7) COMPLIED. |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |