Plan Review Notes For Permit 20080149
Permit Number 20080149
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-13 09:45:51JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16893-R2 IS THE 2014 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE TWO SETS OF 2017 CODE
 VERSION PRODUCT APPROVALS/NOA?S FOR THE PROPOSED
 ACCORDION SHUTTERS.
 2. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
 3. FBC R 310.4. PROVIDE TWO SETS OF FLOOR
 PLANS/BUILDING FOOT PRINT SHOWING LOCATION OF PROPOSED
 ACCORDION SHUTTERS TO BE INSTALLED, SHOW REQUIRED MEANS
 OF ESCAPE. INCLUDE ROOM DESIGNATION.
  