| 2020-08-06 16:10:02 | 08/06/20 1ST GAS/LP REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS |
| | SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL ON THE |
| | DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE |
| | CODE SEC. 61G15-23.005. |
| | |
| | 2. CLEARLY INDICATE ON THE TIE-DOWN CABLE HOW IS IT |
| | PROTECTED FOR THE LP TANK AND APPURTENANCES PER NFPA 58 |
| | AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. SUBMIT DETAILS ON THE TYPE OF CATHODIC PROTECTION, |
| | SIZE (LBS.) & A NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE |
| | OF ANODE CABLE AMOUNT OF WATER TO ACTIVATE IT PER THE |
| | NFPA 58 SEC.6.6.6.1 (J). |
| | |
| | 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 5. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR GENERATOR EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 6. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE 1ST AND 2ND STAGE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC FG |
| | SEC. 410.1. |
| | |
| | 7. PLEASE LABEL AND SHOW ALL UNION IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE OF REGULATOR PER THE 2017 |
| | FBC RES. SEC G2421.2. |
| | |
| | 8. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 9. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017 |
| | FBC RES. SEC. G2419.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |