2020-09-12 08:52:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PERMIT DOCUMENTS FROM ANOTHER PROJECT WERE SUBMITTED
 (20020416). AS THIS ENGINEERING IS SITE SPECIFIC TO THE
 UNIT THIS CANNOT BE USED FOR THIS PROJECT, FBC B 1609.
 PROVIDE ENGINEERING TO SPECIFY WIND DESIGN LOAD
 REQUIREMENTS FOR THIS UNIT.
  
 2. PAGES 1 THROUGH 7 (AND OTHER PAGES AFTER THE SITE
 SPECIFIC ENGINEERING) OF THE PDF UPLOADED APPEAR TO BE
 A PART OF A PRODUCT APPROVAL. PLEASE PROVIDE THE
 PRODUCT APPROVAL IN ITS ENTIRETY, WITH ALL PAGES IN
 ORDER. ALL PAGES ARE REQUIRED TO SHOW CODE COMPLIANCE,
 FBC B 1609.
  
 3. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED
 INSTALLATION, INCLUDING DISTANCE TO THE CORNER OF THE
 BUILDING, IF IT'S A CORNER UNIT, FBC B 1609.
  