| 2020-09-12 08:52:33 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PERMIT DOCUMENTS FROM ANOTHER PROJECT WERE SUBMITTED | | | (20020416). AS THIS ENGINEERING IS SITE SPECIFIC TO THE | | | UNIT THIS CANNOT BE USED FOR THIS PROJECT, FBC B 1609. | | | PROVIDE ENGINEERING TO SPECIFY WIND DESIGN LOAD | | | REQUIREMENTS FOR THIS UNIT. | | | | | | 2. PAGES 1 THROUGH 7 (AND OTHER PAGES AFTER THE SITE | | | SPECIFIC ENGINEERING) OF THE PDF UPLOADED APPEAR TO BE | | | A PART OF A PRODUCT APPROVAL. PLEASE PROVIDE THE | | | PRODUCT APPROVAL IN ITS ENTIRETY, WITH ALL PAGES IN | | | ORDER. ALL PAGES ARE REQUIRED TO SHOW CODE COMPLIANCE, | | | FBC B 1609. | | | | | | 3. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED | | | INSTALLATION, INCLUDING DISTANCE TO THE CORNER OF THE | | | BUILDING, IF IT'S A CORNER UNIT, FBC B 1609. | | | |
|