| 2020-09-10 09:08:59 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20080095 |
| | 9/10/20 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P101 & P103: THE DISTANCES FROM THE SHOWER |
| | TRAPS IN THE MASTER BATH AND BATH-1 TO THE DRY VENTS AT |
| | THE LAVATORIES APPEAR TO BE EXCEEDING THE ALLOWABLE 8 |
| | FT. DISTANCES PER TABLE P3105.1 FBC RES. |
| | |
| | 2) P101 & P103: PLEASE INDICATE A 2 IN. STANDPIPE AT |
| | THE WASHING MACHINE AND A 3 IN. BRANCH DRAIN- SECTION |
| | 406.2 FBC P. |
| | |
| | 3) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & |
| | P2709.2 FBC RES. |
| | |
| | 4) SUBMIT SPECS FOR THE SHOWER AND BATHTUB VALVES- |
| | SECTIONS P2708.4 & P2713.3 FBC RES. |
| | |
| | 5) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | THE GAS PIPING AND FOR THE POOL INSTALLATION- SECTION |
| | 105.1 AND 107.1 WPB. |
| | |
| | 6) PLEASE SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS |
| | AND INSTALLATION MANUALS FOR THE TANKLESS WATER |
| | HEATERS- SECTION G2448.1 FBC RES. THE SPECS SHALL |
| | INCLUDE TEMPERATURE RISE AND GPM FLOW CHARTS TO VERIFY |
| | ACCURATE SIZING |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |