Plan Review Notes
Plan Review Notes For Permit 20080095
Permit Number 20080095
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-10 09:08:591ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20080095
 9/10/20
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P101 & P103: THE DISTANCES FROM THE SHOWER
 TRAPS IN THE MASTER BATH AND BATH-1 TO THE DRY VENTS AT
 THE LAVATORIES APPEAR TO BE EXCEEDING THE ALLOWABLE 8
 FT. DISTANCES PER TABLE P3105.1 FBC RES.
  
 2) P101 & P103: PLEASE INDICATE A 2 IN. STANDPIPE AT
 THE WASHING MACHINE AND A 3 IN. BRANCH DRAIN- SECTION
 406.2 FBC P.
  
 3) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 &
 P2709.2 FBC RES.
  
 4) SUBMIT SPECS FOR THE SHOWER AND BATHTUB VALVES-
 SECTIONS P2708.4 & P2713.3 FBC RES.
  
 5) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE GAS PIPING AND FOR THE POOL INSTALLATION- SECTION
 105.1 AND 107.1 WPB.
  
 6) PLEASE SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUALS FOR THE TANKLESS WATER
 HEATERS- SECTION G2448.1 FBC RES. THE SPECS SHALL
 INCLUDE TEMPERATURE RISE AND GPM FLOW CHARTS TO VERIFY
 ACCURATE SIZING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  