2020-09-11 10:52:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLET SPACING IN SEVERAL ROOMS DOES NOT REFLECT
 2014 CODE (DINING ROOM, OFFICE) 210.52
  
 E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM),
 FROM A RECEPTACLE OUTLET. [210.52(A)(1)]
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN
 WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND
 THAT IS UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND
 SIMILAR OPENINGS, FIREPLACES, AND FIXED CABINETS.
 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS
  
 2) SMOKE ALARM IS MISSING IN STUDIO. R314
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. FBC R314.3, 315.1; FBC 107.2.1
  
  