| Plan Review Notes For Permit 20080095 |
| Permit Number |
20080095 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-11 10:52:48 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) OUTLET SPACING IN SEVERAL ROOMS DOES NOT REFLECT | | | 2014 CODE (DINING ROOM, OFFICE) 210.52 | | | | | | E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO | | | THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR | | | LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM), | | | FROM A RECEPTACLE OUTLET. [210.52(A)(1)] | | | | | | E3901.2.2 WALL SPACE. | | | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE | | | FOLLOWING: [210.52(A)(2)] | | | 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN | | | WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND | | | THAT IS UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND | | | SIMILAR OPENINGS, FIREPLACES, AND FIXED CABINETS. | | | 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR | | | WALLS, EXCLUDING SLIDING PANELS. | | | 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS | | | RAILINGS AND FREESTANDING BAR-TYPE COUNTERS | | | | | | 2) SMOKE ALARM IS MISSING IN STUDIO. R314 | | | | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. FBC R314.3, 315.1; FBC 107.2.1 | | | | | | |
|