| 2020-08-17 14:50:37 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20080092 |
| | 8/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: THE NEW RISER DIAGRAM DOES NOT INCLUDE THE |
| | NEW SANITARY DRAIN AND VENT FOR THE NEW STACKABLE |
| | WASHER/DRYER- SECTION 107.3.5.3 WPB. |
| | |
| | 2) P1: SHOW THE LOCATION OF THE NEW SHUT-OFF VALVES FOR |
| | THE NEW W/D TO VERIFY THEY WILL BE ACCESSIBLE- SECTION |
| | P2903.9.3 FBC RES. |
| | |
| | 3) P1: PROVIDE THE DIMENSIONS OF THE NEW SHOWER- |
| | SECTION P2708.1, AND A CONSTRUCTION DETAIL FOR THE NEW |
| | RECESSED SHOWER AND DRAIN & SECTION P2709.2. |
| | |
| | 4) P1: PLACE NOTES ON THE PLAN TO VERIFY THE O.F.C.I. |
| | SHOWER VALVE AND TUB FAUCET WILL BE IN COMPLIANCE WITH |
| | SECTIONS P2708.4 AND P2713.3: |
| | P2708.4: THE SHOWER VALVE SHALL BE EQUIPPED WITH |
| | CONTROL VALVES OF THE PRESSURE-BALANCE, |
| | THERMOSTATIC-MIXING OR COMBINATION |
| | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A |
| | HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME |
| | A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET |
| | TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN 120 |
| | DEGREES F |
| | P2713.3: HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL |
| | BATHTUBS SHALL BE LIMITED TO A TEMPERATURE OF NOT |
| | GREATER THAN 120 DEGREES F BY A WATER TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |