2020-09-22 11:09:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET I - 514 - THERE APPEARS TO BE NEW DETAIL
 REGARDING THE WALL CLADDING. AS NOTED FOR THE CEILING
 WOOD GRILLE PLEASE PROVIDE A LISTING(IF APPLICABLE) AND
 FIRE RATING PER THE CODE.
 PER NFPA 101, CH 12
  
 12.3.3 INTERIOR FINISH.
 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 12.3.3.3 ASSEMBLY AREAS. INTERIOR WALL AND CEILING
 FINISH
 MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE CLASS A
 OR CLASS
 B IN GENERAL ASSEMBLY AREAS HAVING OCCUPANT LOADS OF
 MORE THAN
 300 AND SHALL BE CLASS A, CLASS B, OR CLASS C IN
 ASSEMBLY AREAS
 HAVING OCCUPANT LOADS OF 300 OR FEWER.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL