| Plan Review Notes For Permit 20080054 |
| Permit Number |
20080054 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-22 11:09:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET I - 514 - THERE APPEARS TO BE NEW DETAIL | | | REGARDING THE WALL CLADDING. AS NOTED FOR THE CEILING | | | WOOD GRILLE PLEASE PROVIDE A LISTING(IF APPLICABLE) AND | | | FIRE RATING PER THE CODE. | | | PER NFPA 101, CH 12 | | | | | | 12.3.3 INTERIOR FINISH. | | | 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | 12.3.3.3 ASSEMBLY AREAS. INTERIOR WALL AND CEILING | | | FINISH | | | MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE CLASS A | | | OR CLASS | | | B IN GENERAL ASSEMBLY AREAS HAVING OCCUPANT LOADS OF | | | MORE THAN | | | 300 AND SHALL BE CLASS A, CLASS B, OR CLASS C IN | | | ASSEMBLY AREAS | | | HAVING OCCUPANT LOADS OF 300 OR FEWER. | | | | | | PLEASE PROVIDE DETAILS IN COMPLIANCE. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|