Plan Review Notes
Plan Review Notes For Permit 20080054
Permit Number 20080054
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-19 12:18:391ST REVIEW FBC-2017 PLUMBING
 PERMIT- 2008054
 8/19/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G-002: THE PLUMBING FIXTURE CALCULATION IS NOT
 IN COMPLIANCE WITH TABLE 403.3 FBC P. PLEASE REVISE THE
 CALCULATIONS IN ACCORDANCE WITH THE TABLE AND NOTE THAT
 THE CALCULATIONS ARE "NOT FOR REFERENCE ONLY", THEY
 SHALL BE SPECIFIC TO THE NEW TENANT OCCUPANCY AND SHALL
 CORRELATE WITH THE TOTAL OCCUPANT LOAD OF THE SPACE,
 AND INCLUDE THE OUTDOOR SEATING LOAD. A) MISSING FROM
 THE CALCULATION FOR A2 OCCUPANCIES ARE THE REQUIRED
 SERVICE SINK AND DRINKING FOUNTAINS. A MINIMUM OF TWO
 DRINKING FOUNTAINS ARE REQUIRED- ONE HIGH AND ONE LOW-
 PER SECTION 410.3 WITH THE EXCEPTION OF RESTAURANTS
 THAT PROVIDE DRINKING WATER IN CONTAINERS FREE OF
 CHARGE- SECTION 410.4. NO NOTE OR STATEMENT HAS BEEN
 PROVIDED ON THE PLAN TO SHOW COMPLIANCE WITH THE
 EXCEPTION. PLEASE PROVIDE CORRECTIONS.
  
 2) I-401: NOTE 3- WATER CLOSET CLEAR FLOOR SPACE
 DIMENSIONS NOT INDICATED- SECTION 604.3.1 FBC ACC.
  
 3) I-401.1: PROVIDE AN ELEVATION VIEW DETAIL SHOWING
 THE REQUIRED KNEE AND TOE CLEARANCES FOR THE LAVATORY
 SINKS- SECTIONS 606.2 AND 306 FBC ACC.
  
 4) I-401.1: PROVIDE THE MOUNTING HEIGHT OF THE TOILET
 PAPER DISPENSER- SECTION 604.7 FBC ACC.
  
 5) I-401.1: REVISE THE HEIGHT OF THE MIRROR NOTE TO
 INDICATE BOTTOM OF REFLECTIVE SURFACE TO BE MAXIMUM 40"
 FROM THE F.F. - SECTION 603.3 FBC ACC.
  
 6) I-401.1: RELOCATE THE WATER CLOSET FLUSH CONTROLS TO
 THE OPEN SIDE OF THE FIXTURE- SECTION 604.6 FBC ACC.
  
 7) G-004: THERE IS NO EQUIPMENT SCHEDULE PROVIDED TO
 CORRELATE WITH THE EQUIPMENT LABELED ON THE PLAN-
 SECTION 107.2.1 WPB.
  
 8) EN-001: ENERGY COMPLIANCE DATA FOR MECHANICAL AND
 PLUMBING NOT PROVIDED- SECTIONS C403 & C404 FBC EC.
  
 9) P-001: PIPING MATERIALS NOT IDENTIFIED- SECTION
 303.1 FBC P. HOT WATER PIPING INSULATION MATERIAL,
 THICKNESS AND R-VALUE NOT IDENTIFIED- SECTION 607.5.
  
 10) P-112: ACKNOWLEDGED THAT THE GREASE INTERCEPTOR IS
 UNDER SEPARATE PERMIT BY LANDLORD, HOWEVER GREASE WASTE
 CALCULATIONS FOR THE NEW TENANT SPACE ARE REQUIRED PER
 SECTION 1003.3.1. INDICATE THE TYPE OF GREASE OF
 INTERCEPTOR TO BE INSTALLED- HYDROMECHANICAL OR GRAVITY
 TYPE- AND THE MAKE AND MODEL AND TESTING APPROVAL
 STANDARD OF THE INTERCEPTOR ON THE PLAN. REFER TO
 SECTION 1003.3.4 FOR HYDROMECHANICAL FOR APPROVED
 SIZING AND STANDARDS, AND 1003.3.6 FOR GRAVITY SIZING
 AND STANDARDS. PLEASE NOTE THAT A SOLIDS INTERCEPTOR IS
 REQUIRED IF A FOOD WASTE DISPOSER IS INSTALLED- SECTION
 1003.3.2 FBC P.
  
 11) P-601: MAKES, MODEL NUMBERS, AND LISTINGS OF THE
 PLUMBING FIXTURES AND EQUIPMENT ARE NOT COMPLETELY
 PROVIDED IN THE SCHEDULE- SEE SECTIONS 404.1 AND 405
 THROUGH 425. PLEASE NOTE REQUIRED NSF LISTINGS UNDER
 SECTIONS 409.1, 426.1, & 611. A) REFER TO TABLE C404.2
 AND PROVIDE THE EFFICIENCY RATING OF THE A.O. SMITH
 WATER HEATER IN THE SCHEDULE.
  
 12) P-601: PROVIDE A DEVICE SCHEDULE THAT INCLUDES THE
 MAKES, MODELS AND LISTING NUMBERS OF THE WATER HAMMER
 ARRESTORS, MIXING VALVES, AND BACKFLOW PREVENTERS-
 SECTIONS 604.9, 607.1.2, AND TABLE 608.1.
  
 13) P-111 & P-501: THE DRAWINGS DO NOT SHOW THE
 FILTERED WATER SUPPLY LINE RUN TO THE ESPRESSO MACHINES
 AND HOW THE PIPE WILL BE PROTECTED FROM DAMAGE- SECTION
 305.1 FBC P. PLEASE IDENTIFY THE TYPE OF FILTERED WATER
 PIPING- SECTION 303.1 FBC P.
  
 14) P-111: PLEASE AT A LABEL AND A NOTE TO IDENTIFY THE
 LOCATION OF THE RECIRCULATION PUMP- X8019- SECTION
 607.2 FBC P.
  
 15) P-112: FOR CLARITY PLEASE LABEL THE WATER CLOSETS
 AND LAVATORIES IN THE ISOMETRIC DRAWING- SECTION
 107.2.1 WPB.
  
 16) P-501: PROVIDE AN ENLARGED SANITARY DRAINAGE PIPING
 DETAIL FOR THE 3-COMPARTMENT SINKS- SECTION 802.1.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  