| Date |
Text |
| 2020-08-05 12:39:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET G 002.1 - THERE AREA INDICATED AS GREEN AND |
| | WITHIN THE OCCUPANT LOAD CALC'S TABLE AS ASSEMBLY |
| | UNCONCENTRATED REFLECTS AN OCCUPANCY LOAD OF 33; |
| | HOWEVER, THERE ARE 43 SEATS INDICATED. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY NARRATIVE AND WITH |
| | SPECIFIC CODE REFERENCES. |
| | |
| | |
| | |
| | 2) SHEET I 512 - THERE ARE INDICATIONS OF A WOOD GRILLE |
| | SYSTEM; HOWEVER, THERE ARE NO INDICATIONS OF OF PRODUCT |
| | SPECIFICATION SHEETS OR APPLICABLE PRODUCT INFORMATION |
| | MEETING THE REQUIRMENTS OF NFPA. |
| | |
| | PER NFPA 101, CH 12 |
| | |
| | 12.3.3 INTERIOR FINISH. |
| | 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | 12.3.3.3 ASSEMBLY AREAS. INTERIOR WALL AND CEILING |
| | FINISH |
| | MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE CLASS A |
| | OR CLASS |
| | B IN GENERAL ASSEMBLY AREAS HAVING OCCUPANT LOADS OF |
| | MORE THAN |
| | 300 AND SHALL BE CLASS A, CLASS B, OR CLASS C IN |
| | ASSEMBLY AREAS |
| | HAVING OCCUPANT LOADS OF 300 OR FEWER. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | |
| | 3) SHEET A 101 - THERE ARE INDICATIONS OF EXSITING |
| | EXTERIOR DOORS; HOWEVER, THERE DOES NOT APPEAR TO BE AN |
| | EXSITING DOOR SCHEDULE. |
| | |
| | THERE IS NO WAY TO CONFRIM/VERIFY THAT THESE EXISTING |
| | DOORS MEET THE REQUIREMENTS OF NFPA 101, CH 12 & CH 7 |
| | |
| | 12.2.2.2 DOORS. |
| | 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE PROIVDE AN EXTERIOR DOOR SCHEDULE TO INCLUDE |
| | COMPLIANT DOOR HARDWARE AND LOCKS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |