Date Text
2020-08-05 12:39:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 002.1 - THERE AREA INDICATED AS GREEN AND
 WITHIN THE OCCUPANT LOAD CALC'S TABLE AS ASSEMBLY
 UNCONCENTRATED REFLECTS AN OCCUPANCY LOAD OF 33;
 HOWEVER, THERE ARE 43 SEATS INDICATED.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY NARRATIVE AND WITH
 SPECIFIC CODE REFERENCES.
  
  
  
 2) SHEET I 512 - THERE ARE INDICATIONS OF A WOOD GRILLE
 SYSTEM; HOWEVER, THERE ARE NO INDICATIONS OF OF PRODUCT
 SPECIFICATION SHEETS OR APPLICABLE PRODUCT INFORMATION
 MEETING THE REQUIRMENTS OF NFPA.
  
 PER NFPA 101, CH 12
  
 12.3.3 INTERIOR FINISH.
 12.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 12.3.3.3 ASSEMBLY AREAS. INTERIOR WALL AND CEILING
 FINISH
 MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE CLASS A
 OR CLASS
 B IN GENERAL ASSEMBLY AREAS HAVING OCCUPANT LOADS OF
 MORE THAN
 300 AND SHALL BE CLASS A, CLASS B, OR CLASS C IN
 ASSEMBLY AREAS
 HAVING OCCUPANT LOADS OF 300 OR FEWER.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 3) SHEET A 101 - THERE ARE INDICATIONS OF EXSITING
 EXTERIOR DOORS; HOWEVER, THERE DOES NOT APPEAR TO BE AN
 EXSITING DOOR SCHEDULE.
  
 THERE IS NO WAY TO CONFRIM/VERIFY THAT THESE EXISTING
 DOORS MEET THE REQUIREMENTS OF NFPA 101, CH 12 & CH 7
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROIVDE AN EXTERIOR DOOR SCHEDULE TO INCLUDE
 COMPLIANT DOOR HARDWARE AND LOCKS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  