2020-08-22 14:05:16FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PROVIDE RISER DIAGRAM OF SERVICE SHOWING LOCATION OF
 SERVICE, SIZE OF ALL SERVICE EQUIPMENT AND WIRE SIZES,
 215.5
  
 2) PROVIDE FAULT CURRENT CALCULATION A ND RATING FOR
 ALL SERVICE EQUIPMENT AND DOWNSTREAM PANELS. 110.9,
 110,10
  
 3) PROVIDE A NOTE FOR LABELING OF SERVICE EQUIPMENT FOR
 ARC FLASH, AIC, LOCATION OF MAINS. 110.24