2020-11-24 08:31:572ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20080046
 11/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW ARE MARKED AS PASSED ON
 FAILED. NOTES HAVE BEEN ADDED TO FAILED COMMENTS.
  
 1) PASSED. SHEET P1 WHICH IS LISTED IN THE DRAWING
 SCHEDULE ON THE COVER SHEET WAS NOT UPLOADED FOR
 REVIEW. A THOROUGH REVIEW OF THE PLANS CANNOT BE
 COMPLETED AT THIS TIME. PLEASE PROVIDE THE P1 SHEET FOR
 REVIEW- SECTION 107.2.1 WPB.
  
 2) PASSED. SHEET LS1: REFER TO SECTION 301.1 FBC EX AND
 INDICATE WHICH COMPLIANCE METHOD WILL USED FOR THE
 PROPOSED ALTERATION. A THOROUGH REVIEW OF THE PLANS
 CANNOT BE COMPLETED WITH A COMPLIANCE METHOD INDICATED.
  
 3) FAILED. THE ARCHITECTURAL FLOOR PLAN AND ELEVATION
 SHEETS INDICATE THE ALTERED BATHROOMS ARE NOT IN
 COMPLIANCE WITH FBC ACC. PLEASE SEE SECTION 202.3 WHICH
 REQUIRES COMPLETE ACCESSIBILITY COMPLIANCE FOR BATHROOM
 ALTERATIONS UNDER SECTION 213 AND SECTIONS 603 THROUGH
 610. THERE ARE EXCEPTIONS LISTED UNDER SECTION 213.2
 HOWEVER NO EXCEPTION IS CITED ON THE PLAN AND NO
 EXPLANATION HAS BEEN PROVIDED. UNDERSTANDING THAT SOME
 OF THE REQUIRED ACCESSIBILITY DETAILS ARE SHOWN ON THE
 ADA PLAN SHEETS, INDICATED BELOW ARE PLAN REVIEW
 REQUIREMENTS FOR THE ACCESSIBLE BATHROOMS: IN RESPONSE
 TO THE COMMENT THE ARCHITECT IS CITING THE EXCEPTION
 FOR TECHNICAL INFEASIBILITY WHICH IS EXCEPTION 2 UNDER
 SECTION 202.3, AND ALSO SECTION 202.4.2 WHICH IS THE
 SUB-SECTION FOR DISPROPORTIONATE COSTS. CONCERNING
 TECHNICAL INFEASIBILITY THERE IS NO INFORMATION OR
 EVIDENCE PROVIDED ON THE PLANS TO SUPPORT THE
 EXCEPTION. CONCERNING THE CLAIM OF DISPROPORTIONATE
 COSTS, THERE IS NO ITEMIZED ACCESSIBILITY COST
 BREAKDOWN PROVIDED IN ACCORDANCE WITH THE SECTION. THE
 ARCHITECT ALSO STATES THAT THE BATHROOMS ARE BEING MADE
 ACCESSIBLE TO THE MAXIMUM EXTENT FEASIBLE, HOWEVER THE
 PLANS DO NOT INDICATE THEY ARE BEING MADE ACCESSIBLE TO
 THE MAXIUM EXTENT FEASIBLE, AND IT APPEARS FURTHER
 COMPLIANCES MUST BE MET. PLEASE REVIEW SHEETS A2,
 ADA.1.1, ADA 1.2. REVISE SHEET A2 IN ACCORDANCE WITH
 THE COMMENTS LISTED BELOW TO SHOW COMPLIANCE TO THE
 MAXIMUM EXTENT AND IF A COMPLIANCE IS DEEMED
 TECHNICALLY INFEASIBLE, PLEASE PROVIDE AN EXPLANATION.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
  
 C) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SHOWERS PER SECTION 608.2.1 AND FIGURE 608.2.1. THE
 SHOWER COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES
 CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS
 OF OPPOSING SIDES AND SHALL HAVE A 36-INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
  
 D) BATHROOM ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
  
 E) TURNING SPACE DIAMETERS SECTION 304.3.
  
 F) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
  
 G) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
  
 H) HEIGHTS OF THE FRONT RIMS OF THE LAVATORIES FROM THE
 FINISHED FLOOR- SECTION 606.3.
  
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2 AND 306.
  
 J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS AT THE WATER CLOSETS- SECTION 604.5 & 609.4.
  
 K) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SECTION
 604.6.
  
 L) LOCATIONS, CLEARANCE, AND MOUNTING HEIGHTS FOR THE
 TOILET PAPER DISPENSERS- SECTION 604.7.
  
 M) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND
 CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1.
  
 O) LOCATION AND DETAILS FOR INSTALLATION OF THE
 REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3.
  
 REFER TO SECTIONS 467.2.3.21.3 & 467.2.4.6 FBC-17
 BUILDING PRINTED BELOW CONCERNING RESIDENT BATHROOMS IN
 HOSPICE INPATIENT FACILITIES.
 467.2.3.21.3
 ALL SHOWERS LOCATED IN BATHING ROOMS CONNECTED DIRECTLY
 TO THE RESIDENT ROOMS SHALL BE DESIGNED SO THAT A
 SHOWER CHAIR CAN BE EASILY ROLLED IN AND OUT OF THE
 SHOWER AREA.
 467.2.4.6
 GRAB BARS SHALL BE PROVIDED AT ALL PATIENT TOILETS,
 SHOWERS, AND TUBS. THE BARS SHALL HAVE A CLEARANCE OF
 11/2 INCHES (38 MM) TO THE WALLS AND SHALL BE
 SUFFICIENTLY ANCHORED TO SUSTAIN A CONCENTRATED APPLIED
 LOAD OF NOT LESS THAN 250 POUNDS (113 KG).
  
 4) PASSED. SHEET A1: A FORWARD APPROACH IS INDICATED
 FOR THE HAND SINK IN THE FAMILY ROOM. PLEASE PROVIDE A
 DETAIL INDICATING THE REQUIRED KNEE AND TOE CLEARANCES
 PER SECTIONS 606.2 AND 306.
  
 5) PASSED. PLEASE NOTE THAT SANITARY AND WATER
 DISTRIBUTION RISERS AND FLAT LINE DRAWINGS WILL BE
 REQUIRED FOR REVIEW. PLEASE REFER TO SECTION
 107.3.5.1.3 WPB FOR PLUMBING PLAN REVIEW REQUIREMENTS.
  
 NEW COMMENTS.
  
 6) SHEET P1: IT APPEARS THAT KEYNOTE 8 SHOULD REPLACE
 KEYNOTE 5 AT THE SHOWER LOCATIONS- SECTION 107.2.1 WPB.
  
 7) P1: PROVIDE A SHOWER PAN AND DRAIN DETAIL- SECTIONS
 417.5.2.1, 417.5.2.6, AND 1002.1 FBC P.
  
 8) P1: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 9) P1: PROVIDE A WATER HAMMER ARRESTOR AND BACKFLOW
 PREVENTER FOR THE ICE MAKER- SECTIONS 604.9 AND 608.3
 FBC P.
  
 10) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ICE MAKER
 AND SHOW HOW CONDENSATION OR DRAINAGE FROM THE ICE
 MAKER WILL BE DISPOSED OF PER SECTION 314.2 FBC P.
  
 11) PLEASE NOTE THAT A SEPARATE PERMIT AND PLANS ARE
 REQUIRED FOR THE MED GAS SYSTEM ALTERATION. A COMPLETE
 REVIEW HAS NOT BEEN PERFORMED UNDER THIS PERMIT.
  
 12) SUBMIT A SUB-PERMIT APPLICATION FOR PLUMBING-
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  