| 2020-08-28 15:59:33 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20080046 |
| | 8/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1 WHICH IS LISTED IN THE DRAWING SCHEDULE ON |
| | THE COVER SHEET WAS NOT UPLOADED FOR REVIEW. A THOROUGH |
| | REVIEW OF THE PLANS CANNOT BE COMPLETED AT THIS TIME. |
| | PLEASE PROVIDE THE P1 SHEET FOR REVIEW- SECTION 107.2.1 |
| | WPB. |
| | |
| | 2) SHEET LS1: REFER TO SECTION 301.1 FBC EX AND |
| | INDICATE WHICH COMPLIANCE METHOD WILL USED FOR THE |
| | PROPOSED ALTERATION. A THOROUGH REVIEW OF THE PLANS |
| | CANNOT BE COMPLETED WITH A COMPLIANCE METHOD INDICATED. |
| | |
| | 3) THE ARCHITECTURAL FLOOR PLAN AND ELEVATION SHEETS |
| | INDICATE THE ALTERED BATHROOMS ARE NOT IN COMPLIANCE |
| | WITH FBC ACC. PLEASE SEE SECTION 202.3 WHICH REQUIRES |
| | COMPLETE ACCESSIBILITY COMPLIANCE FOR BATHROOM |
| | ALTERATIONS UNDER SECTION 213 AND SECTIONS 603 THROUGH |
| | 610. THERE ARE EXCEPTIONS LISTED UNDER SECTION 213.2 |
| | HOWEVER NO EXCEPTION IS CITED ON THE PLAN AND NO |
| | EXPLANATION HAS BEEN PROVIDED. UNDERSTANDING THAT SOME |
| | OF THE REQUIRED ACCESSIBILITY DETAILS ARE SHOWN ON THE |
| | ADA PLAN SHEETS, INDICATED BELOW ARE TYPICAL PLAN |
| | REVIEW REQUIREMENTS FOR THE ACCESSIBLE BATHROOMS: |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | NEW SHOWERS PER SECTION 608.2.1 AND FIGURE 608.2.1. THE |
| | SHOWER COMPARTMENT SHALL BE 36 INCHES BY 36 INCHES |
| | CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS |
| | OF OPPOSING SIDES AND SHALL HAVE A 36-INCH WIDE MINIMUM |
| | ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE |
| | OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM |
| | MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED. |
| | D) BATHROOM ENTRY DOOR WIDTHS, DOOR SWING, AND |
| | WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3. |
| | E) TURNING SPACE DIAMETERS SECTION 304.3. |
| | F) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | G) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOOR- SECTION 604.4. |
| | H) HEIGHTS OF THE FRONT RIMS OF THE LAVATORIES FROM THE |
| | FINISHED FLOOR- SECTION 606.3 |
| | I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2 AND 306. |
| | J) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 & 609.4. |
| | K) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SECTION |
| | 604.6. |
| | L) LOCATIONS, CLEARANCE, AND MOUNTING HEIGHTS FOR THE |
| | TOILET PAPER DISPENSERS- SECTION 604.7. |
| | M) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3 |
| | N) NEW SHOWER GRAB BAR AND SHOWER CONTROL LOCATIONS AND |
| | CLEARANCES PER SECTIONS AND FIGURES 608.3.1 & 608.5.1. |
| | O) LOCATION AND DETAILS FOR INSTALLATION OF THE |
| | REQUIRED SEAT IN THE SHOWER- SECTION 608.4 & 610.3. |
| | |
| | 4) SHEET A1: A FORWARD APPROACH IS INDICATED FOR THE |
| | HAND SINK IN THE FAMILY ROOM. PLEASE PROVIDE A DETAIL |
| | INDICATING THE REQUIRED KNEE AND TOE CLEARANCES PER |
| | SECTIONS 606.2 AND 306. |
| | |
| | 5) PLEASE NOTE THAT SANITARY AND WATER DISTRIBUTION |
| | RISERS AND FLAT LINE DRAWINGS WILL BE REQUIRED FOR |
| | REVIEW. PLEASE REFER TO SECTION 107.3.5.1.3 WPB FOR |
| | PLUMBING PLAN REVIEW REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |