Plan Review Notes
Plan Review Notes For Permit 20080046
Permit Number 20080046
Review Stop M
Sequence Number 1
Notes
Date Text
2020-09-09 16:23:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20080046
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: REGISTERS IN THE RESIDENT AND FAMILY ROOMS
 ARE SYMBOL (C) IN THE DIFFUSER AND REGISTER SCHEDULE ON
 SHEET M0 INDICATING THEY ARE FOR SUPPLY AIR. IN THE
 HVAC LEGEND THE SYMBOL USED INDICATES THIS IS A
 RETURN/EXHAUST GRILLE, PLEASE BE CONSISTENT AND LABEL
 CORRECTLY. FBC FS 107.2.1
  
 2) SHEET M1: THE NEW DUCTWORK IN THE RESIDENTIAL AND
 FAMILY ROOMS ARE SMALLER THAN THE DUCT WORK THAT WAS
 EXISTING. PLEASE SHOW CALCULATIONS SHOWING WE ARE
 GETTING THE SAME ACH IN THESE AREAS. FBC M 407; ASHRAE
 170
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  