2020-08-19 14:43:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 680.26 EQUIPOTENTIAL BONDING (A) PERFORMANCE. THE
 EQUIPOTENTIAL BONDING REQUIRED BY THIS SECTION SHALL BE
 INSTALLED TO REDUCE VOLTAGE GRADIENTS IN THE POOL AREA.
 (B) BONDED PARTS. THE PARTS SPECIFIED IN 680.26(B)(1)
 THROUGH (B)(7) SHALL BE BONDED TOGETHER USING SOLID
 COPPER CONDUCTORS, INSULATED COVERED, OR BARE, NOT
 SMALLER THAN 8 AWG OR WITH RIGID METAL CONDUIT OF BRASS
 OR OTHER IDENTIFIED CORROSI ON-RESISTANT METAL.
  
 POOL LIGHTS LOOK AS IF THEY WERE REPLACED, NEED TO SHOW
 WHAT TYPE OF FIXTURES ARE BEING USED.
  