| Plan Review Notes For Permit 20071503 |
| Permit Number |
20071503 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-05 10:15:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS NO SCOPE OF WORK SUBMITTED. | | | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK. | | | | | | | | | | | | 2) THE APPLICATION INDICATES A CHANGE OF ANNUCIATOR; | | | HOWEVER, THE PLAN SHEET APPEARS TO SHOW SD THAT ARE | | | CIRCLED AND NO INDICATION OF AN | | | ANNUNCIATOR/ANNUNCIATION EQUIPMENT. | | | | | | PLEASE REVIEW AND CONFIRM THE SCOPE OF WORK AND | | | ACCURATELY RELFECT IT ON THE PLAN SHEET. | | | | | | | | | | | | 2A) PLEASE PROVIDE EXISTING LOCATIONS AND NEW LOCATIONS | | | | | | PROVIDE DETAILS. | | | | | | | | | | | | 2B) IS ANY OF THE PROPOESD WORK INVLOVE NEW EQUIPMENT | | | AND WIRING OR MOVING EXISTING? | | | | | | PLEASE PROVIDE A STATEMENT AND PROVIDE EQUIPMENT | | | SPECIFICATION SHEETS. | | | | | | | | | | | | 3) IS ANY OF THE PROPOSED WORK TIED INTO THE THE ANY | | | EXISTING FIRE ALARM SYSTEM/EQUIPMET. | | | | | | PLEASE PROVIDE A STATEMENT | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|