| Plan Review Notes For Permit 20071488 |
| Permit Number |
20071488 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-12-14 08:03:10 | ROOFED PATIO | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 3RD REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) MASONRY WALLS ARE SUBJECT TO WIND LOADS - PLEASE | | | SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN ON THE | | | MASONRY WALL DRAWINGS- FBC 1603.1.4 | | | 2) BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING (A0.0) | | | NEEDS TO BE FOR THE ENTIRE BUILDING. (VB - SPRINKLERED) | | | - DRAWING SHOWS NON-SPRINKLERED | | | 3) WIND DESIGN SPEED SHOWN ON THE ALUMINUM SCREEN ROOM | | | CALCULATIONS SHOULD BE (180MPH) PER FBC WPB AMENDMENTS | | | 120.1 | | | 4) PLEASE PROVIDE SCREEN ROOM DRAWINGS OR PROVIDE IN | | | WRITING THAT THEY ARE TO BE DEFERRED.FBC 107.3.4.1 | | | | | | | | | |
|