| 2020-09-29 10:58:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | A RESPONSE TO PREVIOUS COMMENT # 2 WAS NOT CLEARLY |
| | ADDRESSED WHICH HAS BEEN RESUBMITTED BELOW: |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF AN EXISTING FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEM. WITH THE CREATION OF |
| | THIS NEW OCCUPIABLE INDOOR SPACE, THE LIFE SAFETY |
| | SYSTEMS SHALL BE EXTENDED. |
| | |
| | PER NFPA 101, CH 4 |
| | |
| | 4.6.7 BUILDING REHABILITATION. |
| | 4.6.7.1 REHABILITATION WORK ON EXISTING BUILDINGS SHALL |
| | BE |
| | CLASSIFIED AS ONE OF THE FOLLOWING WORK CATEGORIES IN |
| | ACCORDANCE |
| | WITH 43.2.2.1: |
| | (1) REPAIR |
| | (2) RENOVATION |
| | (3) MODIFICATION |
| | (4) RECONSTRUCTION |
| | (5) CHANGE OF USE OR OCCUPANCY CLASSIFICATION |
| | (6) ADDITION |
| | |
| | 43.8.3 FIRE PROTECTION SYSTEMS. IN OTHER THAN ONE- AND |
| | TWOFAMILY |
| | DWELLINGS, EXISTING COMPARTMENT AREAS WITHOUT AN |
| | APPROVED SEPARATION FROM THE ADDITION SHALL BE |
| | PROTECTED BY AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM WHERE THE COMBINED |
| | AREAS |
| | WOULD BE REQUIRED TO BE SPRINKLERED BY THE PROVISIONS |
| | APPLICABLE |
| | TO NEW CONSTRUCTION FOR THE OCCUPANCY. |
| | |
| | PLEASE PROVIDE DETAILS, CORRECT OR JUSTIFY WITH |
| | SPECIFIC CODE REFERENCES AND NARRATIVE. |
| | |
| | ANY WORK ON THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS |
| | SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | ADDITIONAL COMMENT: |
| | |
| | 2A) PER NFPA 13 INSTALLATION OF FIRE SPRINKLERS |
| | |
| | CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY |
| | AN |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE |
| | PROVIDED WITH |
| | SPRINKLERS IN ALL AREAS EXCEPT WHERE SPECIFIC SECTIONS |
| | OF THIS |
| | STANDARD PERMIT THE OMISSION OF SPRINKLERS. |
| | |
| | CHAPTER 8 INSTALLATION REQUIREMENTS |
| | 8.1* BASIC REQUIREMENTS. |
| | 8.1.1* THE REQUIREMENTS FOR SPACING, LOCATION, AND |
| | POSITION OF |
| | SPRINKLERS SHALL BE BASED ON THE FOLLOWING PRINCIPLES: |
| | (1) SPRINKLERS SHALL BE INSTALLED THROUGHOUT THE |
| | PREMISES. |
| | |
| | (4) SPRINKLERS SHALL BE PERMITTED TO BE OMITTED FROM |
| | AREAS |
| | SPECIFICALLY ALLOWED BY THIS STANDARD. |
| | |
| | THERE IS NO SPECIFIC OMMITTANCE FOR THE PROPOSED. |
| | |
| | |
| | NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE |
| | |
| | CHAPTER 10 FUNDAMENTALS |
| | 10.1 APPLICATION. |
| | 10.1.1 THE BASIC FUNCTIONS OF A COMPLETE FIRE ALARM |
| | AND/OR |
| | SIGNALING SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF |
| | THIS |
| | CHAPTER. |
| | |
| | 10.2 PURPOSE. THE PURPOSE OF FIRE ALARM AND SIGNALING |
| | SYSTEMS |
| | SHALL BE PRIMARILY TO PROVIDE NOTIFICATION OF ALARM, |
| | SUPERVISORY, |
| | AND TROUBLE CONDITIONS; TO ALERT THE OCCUPANTS; TO |
| | SUMMON |
| | AID; AND TO CONTROL EMERGENCY CONTROL FUNCTIONS. |
| | |
| | THERE SHALL BE INITIATION AND NOTIFICATION IN THE NEW |
| | PROPOSED AREA. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC ACKNOWLEDGEMENT TO |
| | PROVIDE SPRINKLER AND ALARM SHOP DRAWING ON THE LIFE |
| | SAFETY SHEET OR PROVIDE SPECIFIC CODE REFERENCES AND A |
| | DETAILED NARRATIVE FOR OMMITTANCE. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |