Plan Review Notes
Plan Review Notes For Permit 20071488
Permit Number 20071488
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-07 08:54:56ROOFED PATIO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE ROOFED PATIO IS PART OF THE "FIRE AREA" AND IS
 REQUIRED TO BE SPRINKLERED. FBC CHAPTER 2 - FIRE AREA.
 THE AGGREGATE FLOOR AREA ENCLOSED AND BOUNDED BY FIRE
 WALLS, FIRE BARRIERS, EXTERIOR WALLS OR HORIZONTAL
 ASSEMBLIES OF A BUILDING. AREAS OF THE BUILDING NOT
 PROVIDED WITH SURROUNDING WALLS SHALL BE INCLUDED IN
 THE FIRE AREA IF SUCH AREAS ARE INCLUDED WITHIN THE
 HORIZONTAL PROJECTION OF THE ROOF OR FLOOR NEXT ABOVE.
 903.2.1.2 GROUP A-2.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR
 FIRE AREAS CONTAINING GROUP A-2 OCCUPANCIES AND
 INTERVENING FLOORS OF THE BUILDING WHERE ONE OF THE
 FOLLOWING CONDITIONS EXISTS: (2).THE FIRE AREA HAS AN
 OCCUPANT LOAD OF 100 OR MORE
 EXCEPTION: A RESTAURANT, CAFETERIA, OR SIMILAR DINING
 FACILITY, INCLUDING AN ASSOCIATED COMMERCIAL KITCHEN,
 IS REQUIRED TO HAVE SPRINKLERS ONLY IF IT HAS A FIRE
 AREA OCCUPANCY LOAD OF 200 PATRONS OR MORE.
 2) MASONRY WALLS ARE SUBJECT TO WIND LOADS - PLEASE
 SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN - FBC
 1603.1.4
 3) BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING (A0.0)
 NEEDS TO BE FOR THE ENTIRE BUILDING. (VB - SPRINKLERED)
 4) WIND DESIGN SPEED SHOWN ON THE ALUMINUM SCREEN ROOM
 CALCULATIONS SHOULD BE (180MPH) PER FBC WPB AMENDMENTS
 120.1
 5) PLEASE PROVIDE SCREEN ROOM DRAWINGS OR PROVIDE IN
 WRITING THAT THEY ARE TO BE DEFERRED.FBC 107.3.4.1
  
 FYI = FBC 901.7 FIRE AREAS.
 WHERE BUILDINGS, OR PORTIONS THEREOF, ARE DIVIDED INTO
 FIRE AREAS SO AS NOT TO EXCEED THE LIMITS ESTABLISHED
 FOR REQUIRING A FIRE PROTECTION SYSTEM IN ACCORDANCE
 WITH THIS CHAPTER, SUCH FIRE AREAS SHALL BE SEPARATED
 BY FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION
 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711, OR BOTH, HAVING A FIRE-RESISTANCE
 RATING OF NOT LESS THAN THAT DETERMINED IN ACCORDANCE
 WITH SECTION 707.3.10.
  