| Date |
Text |
| 2020-10-07 08:54:56 | ROOFED PATIO |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | 2ND REVIEW |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) THE ROOFED PATIO IS PART OF THE "FIRE AREA" AND IS |
| | REQUIRED TO BE SPRINKLERED. FBC CHAPTER 2 - FIRE AREA. |
| | THE AGGREGATE FLOOR AREA ENCLOSED AND BOUNDED BY FIRE |
| | WALLS, FIRE BARRIERS, EXTERIOR WALLS OR HORIZONTAL |
| | ASSEMBLIES OF A BUILDING. AREAS OF THE BUILDING NOT |
| | PROVIDED WITH SURROUNDING WALLS SHALL BE INCLUDED IN |
| | THE FIRE AREA IF SUCH AREAS ARE INCLUDED WITHIN THE |
| | HORIZONTAL PROJECTION OF THE ROOF OR FLOOR NEXT ABOVE. |
| | 903.2.1.2 GROUP A-2. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR |
| | FIRE AREAS CONTAINING GROUP A-2 OCCUPANCIES AND |
| | INTERVENING FLOORS OF THE BUILDING WHERE ONE OF THE |
| | FOLLOWING CONDITIONS EXISTS: (2).THE FIRE AREA HAS AN |
| | OCCUPANT LOAD OF 100 OR MORE |
| | EXCEPTION: A RESTAURANT, CAFETERIA, OR SIMILAR DINING |
| | FACILITY, INCLUDING AN ASSOCIATED COMMERCIAL KITCHEN, |
| | IS REQUIRED TO HAVE SPRINKLERS ONLY IF IT HAS A FIRE |
| | AREA OCCUPANCY LOAD OF 200 PATRONS OR MORE. |
| | 2) MASONRY WALLS ARE SUBJECT TO WIND LOADS - PLEASE |
| | SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN - FBC |
| | 1603.1.4 |
| | 3) BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING (A0.0) |
| | NEEDS TO BE FOR THE ENTIRE BUILDING. (VB - SPRINKLERED) |
| | 4) WIND DESIGN SPEED SHOWN ON THE ALUMINUM SCREEN ROOM |
| | CALCULATIONS SHOULD BE (180MPH) PER FBC WPB AMENDMENTS |
| | 120.1 |
| | 5) PLEASE PROVIDE SCREEN ROOM DRAWINGS OR PROVIDE IN |
| | WRITING THAT THEY ARE TO BE DEFERRED.FBC 107.3.4.1 |
| | |
| | FYI = FBC 901.7 FIRE AREAS. |
| | WHERE BUILDINGS, OR PORTIONS THEREOF, ARE DIVIDED INTO |
| | FIRE AREAS SO AS NOT TO EXCEED THE LIMITS ESTABLISHED |
| | FOR REQUIRING A FIRE PROTECTION SYSTEM IN ACCORDANCE |
| | WITH THIS CHAPTER, SUCH FIRE AREAS SHALL BE SEPARATED |
| | BY FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION |
| | 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 711, OR BOTH, HAVING A FIRE-RESISTANCE |
| | RATING OF NOT LESS THAN THAT DETERMINED IN ACCORDANCE |
| | WITH SECTION 707.3.10. |
| | |