| Plan Review Notes For Permit 20071430 |
| Permit Number |
20071430 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-05 15:29:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THIS IS A REVISION TO PERMIT #18100338, THE WALKIN | | | COOLER BUILDING AND DUMPSTER ENCLOSURE ARE NOT INCLUDED | | | WITH THIS PERMIT. THE WALKIN COOLER BUILDING AND THE | | | DUMPSTER ENCLOSURE DRAWINGS WERE SUBMITTED UNDER PERMIT | | | NUMBER 17020359. ANY REVISIONS TO THESE TWO STRUCTURES | | | SHOULD BE MADE TO THE PERMIT THEY WERE INCLUDED IN. | | | PLEASE REMOVE THESE DRAWINGS FROM THE REVISION AND | | | SUBMIT THEM AS A REVISION TO THE APPROPRIATE PERMIT. | | | FBC 107.2 | | | | | | 2) REVISED SHEET A-101R NO LONGER SHOWS THE ACCESSIBLE | | | PORTION OF THE BAR THAT IS REQUIRED BY FBC | | | ACCESSIBILITY SECTION 902.1. |
|