2020-08-05 15:29:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS IS A REVISION TO PERMIT #18100338, THE WALKIN
 COOLER BUILDING AND DUMPSTER ENCLOSURE ARE NOT INCLUDED
 WITH THIS PERMIT. THE WALKIN COOLER BUILDING AND THE
 DUMPSTER ENCLOSURE DRAWINGS WERE SUBMITTED UNDER PERMIT
 NUMBER 17020359. ANY REVISIONS TO THESE TWO STRUCTURES
 SHOULD BE MADE TO THE PERMIT THEY WERE INCLUDED IN.
 PLEASE REMOVE THESE DRAWINGS FROM THE REVISION AND
 SUBMIT THEM AS A REVISION TO THE APPROPRIATE PERMIT.
 FBC 107.2
  
 2) REVISED SHEET A-101R NO LONGER SHOWS THE ACCESSIBLE
 PORTION OF THE BAR THAT IS REQUIRED BY FBC
 ACCESSIBILITY SECTION 902.1.