| 2020-08-31 15:31:19 | 08/31/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR |
| | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1. |
| | |
| | 2. PLEASE CLARIFY IF LINE IS FROM METER TO HOUSE, FPU |
| | WONT INSTALL A METER SO IF THIS LINE IS RAN IT MUST |
| | HAVE A VALVE AND CAP AT THE END. PLEASE PROVIDE SIZE OF |
| | PIPE, TYPE OF PIPE, PRESSURE FROM METER, HOW MANY BTU'S |
| | TO EACH APPLIANCE AND LENGTH TO SERVICE THE LAST RUN TO |
| | DETERMINE SUPPLY PIPE SIZE. GAS WILL REQUIRE A PERMIT |
| | AT THIS TIME AND A PERMIT FOR ROUGH IN SO YOU MAY NOT |
| | WANT TO DO GAS AT THIS TIME. |
| | |
| | 3. THERE IS A GAS LINE BUT IN MASTER PLANS NO GAS IS |
| | PRESENT PLEASE CLARIFY WHY THIS IS SO AND IF GAS REVIEW |
| | IS REQUIRED IT MUST BE NOTED ON THE MASTER SET OR A |
| | REVISION WILL HAVE TO BE SUBMITTED AT A LATER DATE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE DETAIL DESCRIPTIVE OF |
| | MATERIALS, LABOR, SHOW DETAILED, QUANTITY ESTIMATES TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL PER THE WPB |
| | AMENDMENTS TO THE FBC 109.3. BUILDING PERMITS |
| | VALUATIONS. |
| | |
| | 5. THE PHYSICAL ADDRESS NUMBER OF THE RESIDENCE MUST BE |
| | ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. SEWER LINE REQUIRES A CLEAN OUT AT CITY TAP IF ONE |
| | IS NOT PRESENT BY CITY AT LATERAL CONNECTION. THE SEWER |
| | MUST BE SUBBED UP AND HARD CAPPED NEXT TO HOME |
| | CONNECTION. |
| | |
| | 7. THE WATER SERVICE MUST HAVE A REDUCED PRESSURE ZONE |
| | VACUUM BREAKER AT METER AND A SEPARATE PERMIT IS |
| | REQUIRED WITH CERTIFICATION OF THE CITY OF WEST PALM |
| | BEACH UTILITIES DEPARTMENT AND A FINAL INSPECTION BY |
| | PLUMBING DEPARTMENT PER THE 2017 FBC SEC. R 2902.1 AND |
| | THE CITY OF WEST PALM BEACH CROSS CONNECTION PROGRAM. |
| | NOTE ANY CONSTRUCTION PROJECT WILL REQUIRE AN RPZ AT |
| | METER PER THE CITY OF WPB CCP. |
| | |
| | 8. THE WATER LINE RAN MUST BE A MINIMUM 3/4 " TO THE |
| | BACK OF HOUSE PER THE 2017 FBC SEC. R 2903.7. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |