Plan Review Notes For Permit 20071429
Permit Number 20071429
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-31 15:31:1908/31/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 2. PLEASE CLARIFY IF LINE IS FROM METER TO HOUSE, FPU
 WONT INSTALL A METER SO IF THIS LINE IS RAN IT MUST
 HAVE A VALVE AND CAP AT THE END. PLEASE PROVIDE SIZE OF
 PIPE, TYPE OF PIPE, PRESSURE FROM METER, HOW MANY BTU'S
 TO EACH APPLIANCE AND LENGTH TO SERVICE THE LAST RUN TO
 DETERMINE SUPPLY PIPE SIZE. GAS WILL REQUIRE A PERMIT
 AT THIS TIME AND A PERMIT FOR ROUGH IN SO YOU MAY NOT
 WANT TO DO GAS AT THIS TIME.
  
 3. THERE IS A GAS LINE BUT IN MASTER PLANS NO GAS IS
 PRESENT PLEASE CLARIFY WHY THIS IS SO AND IF GAS REVIEW
 IS REQUIRED IT MUST BE NOTED ON THE MASTER SET OR A
 REVISION WILL HAVE TO BE SUBMITTED AT A LATER DATE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 4. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE DETAIL DESCRIPTIVE OF
 MATERIALS, LABOR, SHOW DETAILED, QUANTITY ESTIMATES TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL PER THE WPB
 AMENDMENTS TO THE FBC 109.3. BUILDING PERMITS
 VALUATIONS.
  
 5. THE PHYSICAL ADDRESS NUMBER OF THE RESIDENCE MUST BE
 ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. SEWER LINE REQUIRES A CLEAN OUT AT CITY TAP IF ONE
 IS NOT PRESENT BY CITY AT LATERAL CONNECTION. THE SEWER
 MUST BE SUBBED UP AND HARD CAPPED NEXT TO HOME
 CONNECTION.
  
 7. THE WATER SERVICE MUST HAVE A REDUCED PRESSURE ZONE
 VACUUM BREAKER AT METER AND A SEPARATE PERMIT IS
 REQUIRED WITH CERTIFICATION OF THE CITY OF WEST PALM
 BEACH UTILITIES DEPARTMENT AND A FINAL INSPECTION BY
 PLUMBING DEPARTMENT PER THE 2017 FBC SEC. R 2902.1 AND
 THE CITY OF WEST PALM BEACH CROSS CONNECTION PROGRAM.
 NOTE ANY CONSTRUCTION PROJECT WILL REQUIRE AN RPZ AT
 METER PER THE CITY OF WPB CCP.
  
 8. THE WATER LINE RAN MUST BE A MINIMUM 3/4 " TO THE
 BACK OF HOUSE PER THE 2017 FBC SEC. R 2903.7.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  