2020-11-20 10:20:561ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20071423
 11/20/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WPB BUILDING DEPT. PLAN RECORDS FOR PERMIT 19041488
 INDICATE AN EXISTING 16 KW AT 309,000 BTUS. THE NEW
 GENERATOR PER THE SPECS IS LISTED AT 492,000. IN ORDER
 TO ENSURE A SAFE OPERATING SYSTEM PLEASE PROVIDE AN
 UPDATED AND COMPLETE GAS RISER DRAWING SHOWING THE
 EXISTING GAS PIPING AND APPLIANCES- SECTIONS G2412.3 &
 G2412.4 FBC RES. PLEASE INCLUDE THE FOLLOWING
 INFORMATION ON THE RISER:
  
 A) SHOW THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF THE
 SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) CLARIFY IF A NEW REGULATOR IS TO BE INSTALLED AS
 PART OF THE UPGRADE. PLEASE NOTE THE SPECS FOR THE NEW
 GENERATOR INDICATE GAS INPUT PRESSURE OF 5- 14 IN. W.C.
 INDICATE THE MAKE AND MODEL OF THE EXISTING OR NEW
 REGULATOR AND NOTE THE INLET AND OUTLET PRESSURE ON THE
 RISER DRAWING- SECTION G2421.1 & G2421.2. SUBMIT MARKED
 UP OR HIGHLIGHTED SPECS SHOWING THE SELECTED MODEL, THE
 MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 AND ORIFICE SIZE. THE SPECS MAY BE DEFERRED AND BE
 ONSITE FOR INSPECTION.
  
 D) SHOW AN EXISTING OR NEW DRIP LEG AND FLEX CONNECTOR
 FOR THE GAS SUPPLY TO THE GENERATOR- SECTIONS- G2419.3
 & G2422.1 FBC RES.
  
 2) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  