| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED SLOPED ROOFING SYSTEM |
| | USED. |
| | 2. SUBMITTED MIAMI-DADE COUNTY NOA NO. 18-1127.18 |
| | GENERAL LIMITATION #7 IS SPECIFICALLY REFERRED TO IN |
| | THIS NOA. PERIMETER AND CORNER AREAS SHALL COMPLY WITH |
| | THE ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE |
| | AREAS. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION AND BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARD RAS 117. CALCULATIONS |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR |
| | REGISTERED ROOF CONSULTANT. PROVIDE. |
| | |