2020-08-11 16:47:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SOME OF THE NEW OUTLETS ARE DESIGNATED AS GFCI, THEY
 CAN BE BUT THEY ALSO NEED TO BE AFCI PROTECTED.
  
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.16
  
 2) OUTLETS IN THE KITCHEN, AND LAUNDRY ROOM TO BE GFCI
 AND AFCI PROTECTED
  
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.16
  
 E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR
 PERSONNEL. [210.8(A)(9)]
  
 E3902.6 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES THAT SERVE COUNTERTOP
 SURFACES SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(6)]
  
 3) COUNTER SPACE IN THE KITCHEN MAY NEED OUTLETS PER
 210.52 NOT SURE WHAT IS COUNTER SPACE AND WHAT IS NOT.
  
 THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE
 STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE3901.
  
 5) ISLAND OUTLET(S) DO NOT APPEAR TO MEET THE CODE
 210.52.
  
 5) LOW VOLTAGE OUTLETS REQUIRE A SEPARATE PERMIT.
  
  
  
  
  
  
  
  
  