| 2020-08-11 16:47:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) SOME OF THE NEW OUTLETS ARE DESIGNATED AS GFCI, THEY |
| | CAN BE BUT THEY ALSO NEED TO BE AFCI PROTECTED. |
| | |
| | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| | LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| | RE3902.16 |
| | |
| | 2) OUTLETS IN THE KITCHEN, AND LAUNDRY ROOM TO BE GFCI |
| | AND AFCI PROTECTED |
| | |
| | ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS, |
| | LAUNDRY ROOMS, FAMILY ROOMS, DINING ROOMS, LIVING |
| | ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC |
| | RE3902.16 |
| | |
| | E3902.9 LAUNDRY AREAS. 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR |
| | PERSONNEL. [210.8(A)(9)] |
| | |
| | E3902.6 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE RECEPTACLES THAT SERVE COUNTERTOP |
| | SURFACES SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. [210.8(A)(6)] |
| | |
| | 3) COUNTER SPACE IN THE KITCHEN MAY NEED OUTLETS PER |
| | 210.52 NOT SURE WHAT IS COUNTER SPACE AND WHAT IS NOT. |
| | |
| | THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE |
| | STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO |
| | THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| | IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS |
| | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC |
| | 210.52(C)(1); FBC RE3901. |
| | |
| | 5) ISLAND OUTLET(S) DO NOT APPEAR TO MEET THE CODE |
| | 210.52. |
| | |
| | 5) LOW VOLTAGE OUTLETS REQUIRE A SEPARATE PERMIT. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |