| 2020-09-04 14:39:32 | PLAN REVIEW - BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE STAIRLIFT INSTALLATION INSTRUCTIONS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. PROVIDE A STRUCTURAL ATTACHMENT DETAIL. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 3. DEMONSTRATE HOW THE MINIMUM STAIRWAY WIDTH PER |
| | R311.7 WILL BE MAINTAINED. |
| | R311.7 STAIRWAYS. |
| | |
| | R311.7.1 WIDTH. |
| | STAIRWAYS SHALL NOT BE LESS THAN 36 INCHES (914 MM) IN |
| | CLEAR WIDTH AT ALL POINTS ABOVE THE PERMITTED HANDRAIL |
| | HEIGHT AND BELOW THE REQUIRED HEADROOM HEIGHT. |
| | HANDRAILS SHALL NOT PROJECT MORE THAN 4.5 INCHES (114 |
| | MM) ON EITHER SIDE OF THE STAIRWAY AND THE MINIMUM |
| | CLEAR WIDTH OF THE STAIRWAY AT AND BELOW THE HANDRAIL |
| | HEIGHT, INCLUDING TREADS AND LANDINGS, SHALL NOT BE |
| | LESS THAN 311/2 INCHES (787 MM) WHERE A HANDRAIL IS |
| | INSTALLED ON ONE SIDE AND 27 INCHES (698 MM) WHERE |
| | HANDRAILS ARE PROVIDED ON BOTH SIDES. |
| | |
| | |