| 2020-08-05 12:15:04 | 1ST REVIEW FBC-2017 PLUMBING/GREASE INTERCEPTOR |
| | PERMIT- 20071347 |
| | 8/5/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 1) P1 & P1.1: PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION. A |
| | PRIMARY PERMIT APPLICATION BY A FL. LICENSED PLUMBER |
| | AND COMPLETE PLUMBING PLANS, SIZING CALCULATIONS, AND |
| | SPECIFICATIONS SHALL BE SUBMITTED- SECTION 107.2.1 WPB. |
| | |
| | 2) P1: REMOVE THE GRAVITY GREASE INTERCEPTOR |
| | CALCULATION TABLE FORM THE PLAN TO AVOID CONFUSION. THE |
| | NEW SELECTED SCHIER GREAT BASIN INTERCEPTORS ARE |
| | HYDROMECHANICAL AND SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION 1003.3.4 FBC P. PROVIDE REVISED CALCULATIONS ON |
| | THE PLAN USING THE REQUIRED METHOD. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |