Plan Review Notes
Plan Review Notes For Permit 20071347
Permit Number 20071347
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2020-08-05 12:15:041ST REVIEW FBC-2017 PLUMBING/GREASE INTERCEPTOR
 PERMIT- 20071347
 8/5/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) P1 & P1.1: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION. A
 PRIMARY PERMIT APPLICATION BY A FL. LICENSED PLUMBER
 AND COMPLETE PLUMBING PLANS, SIZING CALCULATIONS, AND
 SPECIFICATIONS SHALL BE SUBMITTED- SECTION 107.2.1 WPB.
  
 2) P1: REMOVE THE GRAVITY GREASE INTERCEPTOR
 CALCULATION TABLE FORM THE PLAN TO AVOID CONFUSION. THE
 NEW SELECTED SCHIER GREAT BASIN INTERCEPTORS ARE
 HYDROMECHANICAL AND SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 1003.3.4 FBC P. PROVIDE REVISED CALCULATIONS ON
 THE PLAN USING THE REQUIRED METHOD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  