| Date |
Text |
| 2020-08-05 11:34:03 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20071347 |
| | 8/5/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED." |
| | 1) SHEET A-1: THE 4'8" DEPTH SHOWN FOR THE STANDARD |
| | WATER CLOSET COMPARTMENT IN THE MEN'S RESTROOM IS NOT |
| | IN COMPLIANCE WITH SECTION 405.33.1 FBC P. THE REQUIRED |
| | DEPTH IS 60" FOR TANK TOILETS. PLEASE SHOW THE DEPTH |
| | MEASUREMENTS IN THE WOMEN'S RESTROOMS. |
| | |
| | 2) P1 & P1.1: PLEASE NOTE THAT A SEPARATE PERMIT IS |
| | REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION. A |
| | PRIMARY PERMIT APPLICATION BY A FL. LICENSED PLUMBER |
| | AND COMPLETE PLUMBING PLANS, SIZING CALCULATIONS, AND |
| | SPECIFICATIONS SHALL BE SUBMITTED- SECTION 107.2.1 WPB. |
| | |
| | 3) P1: REMOVE THE GRAVITY GREASE INTERCEPTOR |
| | CALCULATION TABLE FORM THE PLAN TO AVOID CONFUSION. THE |
| | NEW SELECTED SCHIER GREAT BASIN INTERCEPTORS ARE |
| | HYDROMECHANICAL AND SHALL BE SIZED IN ACCORDANCE WITH |
| | SECTION 1003.3.4 FBC P. PROVIDE REVISED CALCULATIONS ON |
| | THE PLAN USING THE REQUIRED METHOD. |
| | |
| | 4) P2: PLEASE CORRECTLY LABEL THE LOCATION OF THE TMV |
| | IN THE WATER HEATING PIPING DETAIL- SEE BALANCING VALVE |
| | INSTRUCTIONS IN THE DETAIL. PLEASE NOTE THAT WHERE A |
| | THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM WITH A |
| | HOT WATER RECIRCULATING PUMP, THE HOT WATER OR TEMPERED |
| | WATER RETURN LINE SHALL BE ROUTED TO THE COLD WATER |
| | INLET PIPE OF THE WATER HEATER AND THE COLD WATER INLET |
| | PIPE OR THE HOT WATER RETURN CONNECTION OF THE |
| | THERMOSTATIC MIXING VALVE. A) THE LOCATION OF THE |
| | CIRCULATION PUMP IS INCORRECTLY SHOWN ON THE HW SUPPLY |
| | LINE ON THE FLOOR PLAN. |
| | |
| | 5) P2.1 PLEASE CLARIFY WHICH LINE THE CIRCULATION PUMP |
| | IS BEING INSTALLED ON- SEE COMMENT #4 ABOVE. A) SHOW |
| | THE LOCATIONS OF REQUIRED MIXING VALVES AT THE PUBLIC |
| | LAVATORIES- SECTION 416.5 FBC P. B) SHOW THE LOCATIONS |
| | OF BACKFLOW PREVENTERS FOR SUPPLY LINES TO THE SODA |
| | DISPENSERS AND GUNS, ICE MAKERS, ICE STORAGE BINS, |
| | STEAMER, MOP SINK, AND ALL OTHER SUPPLY LINES TO |
| | APPLIANCES OR EQUIPMENT PROVIDING A SPECIAL FUNCTION- |
| | SECTION 608.3. C) SHOW THE LOCATIONS OF REQUIRED WATER |
| | HAMMER ARRESTORS- SECTION 604.9. D) PROVIDE A DEVICE |
| | SCHEDULE THAT INCLUDES THE TYPE OF BACKFLOW PREVENTER |
| | TO BE INSTALLED AT EACH LOCATION- SEE TABLE 608.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |