Plan Review Notes
Plan Review Notes For Permit 20071347
Permit Number 20071347
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-05 11:34:031ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20071347
 8/5/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED."
 1) SHEET A-1: THE 4'8" DEPTH SHOWN FOR THE STANDARD
 WATER CLOSET COMPARTMENT IN THE MEN'S RESTROOM IS NOT
 IN COMPLIANCE WITH SECTION 405.33.1 FBC P. THE REQUIRED
 DEPTH IS 60" FOR TANK TOILETS. PLEASE SHOW THE DEPTH
 MEASUREMENTS IN THE WOMEN'S RESTROOMS.
  
 2) P1 & P1.1: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION. A
 PRIMARY PERMIT APPLICATION BY A FL. LICENSED PLUMBER
 AND COMPLETE PLUMBING PLANS, SIZING CALCULATIONS, AND
 SPECIFICATIONS SHALL BE SUBMITTED- SECTION 107.2.1 WPB.
  
 3) P1: REMOVE THE GRAVITY GREASE INTERCEPTOR
 CALCULATION TABLE FORM THE PLAN TO AVOID CONFUSION. THE
 NEW SELECTED SCHIER GREAT BASIN INTERCEPTORS ARE
 HYDROMECHANICAL AND SHALL BE SIZED IN ACCORDANCE WITH
 SECTION 1003.3.4 FBC P. PROVIDE REVISED CALCULATIONS ON
 THE PLAN USING THE REQUIRED METHOD.
  
 4) P2: PLEASE CORRECTLY LABEL THE LOCATION OF THE TMV
 IN THE WATER HEATING PIPING DETAIL- SEE BALANCING VALVE
 INSTRUCTIONS IN THE DETAIL. PLEASE NOTE THAT WHERE A
 THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM WITH A
 HOT WATER RECIRCULATING PUMP, THE HOT WATER OR TEMPERED
 WATER RETURN LINE SHALL BE ROUTED TO THE COLD WATER
 INLET PIPE OF THE WATER HEATER AND THE COLD WATER INLET
 PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE. A) THE LOCATION OF THE
 CIRCULATION PUMP IS INCORRECTLY SHOWN ON THE HW SUPPLY
 LINE ON THE FLOOR PLAN.
  
 5) P2.1 PLEASE CLARIFY WHICH LINE THE CIRCULATION PUMP
 IS BEING INSTALLED ON- SEE COMMENT #4 ABOVE. A) SHOW
 THE LOCATIONS OF REQUIRED MIXING VALVES AT THE PUBLIC
 LAVATORIES- SECTION 416.5 FBC P. B) SHOW THE LOCATIONS
 OF BACKFLOW PREVENTERS FOR SUPPLY LINES TO THE SODA
 DISPENSERS AND GUNS, ICE MAKERS, ICE STORAGE BINS,
 STEAMER, MOP SINK, AND ALL OTHER SUPPLY LINES TO
 APPLIANCES OR EQUIPMENT PROVIDING A SPECIAL FUNCTION-
 SECTION 608.3. C) SHOW THE LOCATIONS OF REQUIRED WATER
 HAMMER ARRESTORS- SECTION 604.9. D) PROVIDE A DEVICE
 SCHEDULE THAT INCLUDES THE TYPE OF BACKFLOW PREVENTER
 TO BE INSTALLED AT EACH LOCATION- SEE TABLE 608.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  