2020-08-05 11:43:051ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20071347
 8/5/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3 GAS RISER: PROVIDE THE SIZING TABLE FOR THE
 0.5" WC PRESSURE PIPING- SECTION 402.4 FBC FG.
  
 2) P3 GAS RISER: SHOW THE LOCATIONS OF REQUIRED UNIONS
 AT THE MP REGULATORS- SECTION 410.2 (7) FBC FG.
  
 3) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 CHINESE RANGE WOK- SECTION 623.1 FBC FG. THE SPECS WERE
 NOT SUBMITTED WITH THE PLANS AND SPECS UNDER PERMIT
 20010651.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  