| 2020-08-05 11:43:05 | 1ST REVIEW FBC-2017 FUEL GAS | | | PERMIT- 20071347 | | | 8/5/2020 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P3 GAS RISER: PROVIDE THE SIZING TABLE FOR THE | | | 0.5" WC PRESSURE PIPING- SECTION 402.4 FBC FG. | | | | | | 2) P3 GAS RISER: SHOW THE LOCATIONS OF REQUIRED UNIONS | | | AT THE MP REGULATORS- SECTION 410.2 (7) FBC FG. | | | | | | 3) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | CHINESE RANGE WOK- SECTION 623.1 FBC FG. THE SPECS WERE | | | NOT SUBMITTED WITH THE PLANS AND SPECS UNDER PERMIT | | | 20010651. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|