2020-08-18 10:43:41FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) A PLAN SHOWING THE REQUIRED LABELS SHALL BE
 PROVIDED.
  
 690.31(G)(3) MARKING AND LABELING REQUIRED.
 690.31(G)(4) MARKING AND LABELING METHODS AND
 LOCATIONS.
  
  
 2) NEUTRAL CONDUCTOR CAN NOT BE BONDED TO THE ENCLOSURE
 IN THE COMBINER PANEL. 250.24 (A)(5) LOAD-SIDE
 GROUNDING CONNECTIONS. A GROUNDED CONDUCTOR SHALL NOT
 BE CONNECTED TO NORMALLY NON?CURRENTCARRYING METAL
 PARTS OF EQUIPMENT, TO EQUIPMENT GROUNDING
 CONDUCTOR(S), OR BE RECONNECTED TO GROU ND ON THE LOAD
 SIDE OF THE SERVICE DISCONNECTING MEANS EXCEPT AS
 OTHERWISE PERMITTED IN THIS ARTICLE.
  