| Plan Review Notes For Permit 20071339 |
| Permit Number |
20071339 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-18 10:43:41 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) A PLAN SHOWING THE REQUIRED LABELS SHALL BE | | | PROVIDED. | | | | | | 690.31(G)(3) MARKING AND LABELING REQUIRED. | | | 690.31(G)(4) MARKING AND LABELING METHODS AND | | | LOCATIONS. | | | | | | | | | 2) NEUTRAL CONDUCTOR CAN NOT BE BONDED TO THE ENCLOSURE | | | IN THE COMBINER PANEL. 250.24 (A)(5) LOAD-SIDE | | | GROUNDING CONNECTIONS. A GROUNDED CONDUCTOR SHALL NOT | | | BE CONNECTED TO NORMALLY NON?CURRENTCARRYING METAL | | | PARTS OF EQUIPMENT, TO EQUIPMENT GROUNDING | | | CONDUCTOR(S), OR BE RECONNECTED TO GROU ND ON THE LOAD | | | SIDE OF THE SERVICE DISCONNECTING MEANS EXCEPT AS | | | OTHERWISE PERMITTED IN THIS ARTICLE. | | | |
|